2. Freeze-up prevention, vacuum pump continuous running control
•
•
•
•
Avoid freeze-up in tube by vacuum pump continuous running at low outdoor temp.
•
•
•
•
Start condition
a. OD temp status 1(a,b)
b. O
2
supply level
0
•
•
•
•
Control content
a. Continuous running disregard of oxygen supply level
•
•
•
•
Cancellation condition
−
−
−
−
Start condition not fulfilled
•
•
•
•
Exceptional condition
During deice & MOPMPS08 after deice, OD temp. status does not update as the OD fan is stop. (Air temp. detection
disable).
3. Freeze-up prevention, 2 way valve control
•
•
•
•
Open valve periodically to prevent freeze-up during low OD air temp.
•
•
•
•
Open valve duration change according to air temp. status (1a or 1b).
a. Start condition
Either one of below condition is fulfilled.
i. O
2
supply leve
0 & OD air temp status shift to 1(a,b).
49
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
Содержание CS-XE9CKE
Страница 10: ...4 Dimensions 10 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 11: ...11 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 13: ...6 Block Diagram 13 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 14: ...7 Wiring Diagram 14 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 91: ...13 Technical Data 91 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 92: ...92 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 104: ...104 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 105: ...How to use electronic circuit diagram 105 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 106: ...18 1 REMOTE CONTROL 106 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 107: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 107 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Страница 109: ...18 5 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD MAIN 109 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...