Hot Start Control
Anti Cold Draft Control
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
Hot Start is completed when indoor heat exchanger rises to 39°C or over 4 minutes.
•
This operation is to prevent the Cold Draft during Heating mode operation.
•
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
•
For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
•
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
•
Anti Cold Draft Control will stop when:
−
Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
−
After 30 minutes time saved control.
(refer to next page).
24
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5