Vertical Airflow Direction Auto-Control
•
When set a Airflow Direction Auto-Control with remote
control, the louver swings up and down as shown in the
diagram.
•
The louver does not swing when the Indoor Fan Motor
stops during operation at the upper limit.
•
When stopped with remote control, the discharge vent is
reset, and stopped at the closing position.
•
During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 36° to 12° - 28° under
Cooling and Soft Dry operation mode.
Vertical Airflow Direction manual Control
•
When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
•
When the remote control is used to stop the operation, the
discharge vent is reset, and stopped at the closing position.
•
During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 14°, 19°, 24°, 30°, 36° to
16°, 18°, 20°, 22°, 24° under Cooling and Soft Dry operation
mode.
Horizontal Airflow Direction Auto-Control
•
When set a Airflow Direction Auto-Control with remote
control, the vanes swings left and right as shown in the
diagram.
•
The vanes does not swing when the Indoor Fan Motor stops
during operation at 22° angle.
•
When stopped with remote control, the discharge vent is
reset, and stopped at the reset position.
•
During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 44° to 14° - 30° under
Cooling and Soft Dry operation mode.
8.8. Airflow Direction Control
1. There is no swinging while indoor fan motor is stopped during Cooling and Soft Dry operation.
2. When the intake air temperature reaches 38°C, the louver is changed from upper to lower limit. When the intake air temperature falls to
35°C, the louver is changed from louver to upper limit.
1. There is no swinging while indoor fan motor is stopped during Cooling and Soft Dry operation.
2. In Heating operation, when the intake air temperature reaches set temperature, the airflow direction is Auto Swing left and right. When
the intake air temperature falls to 2°C lower than set temperature, the airflow direction is stop at 22° angle.
26
CS-W18CKP CU-W18CKP5 / CS-W24CKP CU-W24CKP5
Содержание CS-W18CKP
Страница 10: ...4 Dimensions 10 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 11: ...11 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 13: ...6 Block Diagram 13 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 14: ...7 Wiring Diagram CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 14 ...
Страница 18: ...Soft Dry Operation Time Diagram 18 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 22: ...a Normal Deicing Time Diagram b Overload Deicing Time Diagram 22 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 62: ...14 Technical Data 62 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 64: ...64 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 65: ...65 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 74: ...19 1 REMOTE CONTROL 74 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 75: ...19 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 75 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 76: ...19 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 76 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...