Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Anti-Freezing Control
•
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
•
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
8 Operation Details
8.1. Cooling Mode Operation
•
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
•
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
•
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
▲
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
•
Purpose is to prevent dew formation on indoor unit air discharge area.
•
When the following conditions occur for 30 minutes continuously, anti-dew formation is controlled by indoor fan speed shift to
low (Changed to Lo
+
):
−
Indoor intake air temperature is more than 24°C and less than 30°C.
−
Remote Control setting temperature is less than 25°C.
−
Compressor is on.
−
Cooling operation mode.
−
Indoor Fan motor operate at Low fan speed.
•
This control is cancelled immediately when above condition is changed.
15
CS-W18CKP CU-W18CKP5 / CS-W24CKP CU-W24CKP5
Содержание CS-W18CKP
Страница 10: ...4 Dimensions 10 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 11: ...11 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 13: ...6 Block Diagram 13 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 14: ...7 Wiring Diagram CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 14 ...
Страница 18: ...Soft Dry Operation Time Diagram 18 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 22: ...a Normal Deicing Time Diagram b Overload Deicing Time Diagram 22 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 62: ...14 Technical Data 62 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 64: ...64 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 65: ...65 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 74: ...19 1 REMOTE CONTROL 74 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 75: ...19 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 75 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...
Страница 76: ...19 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 76 CS W18CKP CU W18CKP5 CS W24CKP CU W24CKP5 ...