10.3. REFRIGERANT PIPING WORK
10.3.1. Piping Materials
It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10 m. Do not use
pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog
the expansion valves or capillaries.
Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materials that are
appropriate for these standards.
The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing with a thickness of only 0.7
mm is also available on the market, but this should never be used.
Table 10 Copper tube thickness (mm)
Soft pipe
Thickness (mm)
Nominal diameter
Outside diameter (mm)
R410A
(Reference)R22
1/4
6.35
0.80
0.80
3/8
9.52
0.80
0.80
1/2
12.7
0.80
0.80
10.3.2. Processing and Connecting Piping Materials
When working with refrigerant piping, the following points must be carefully observed: no moisture or dust must be allowed to enter
the piping, and there must be no refrigerant leaks.
1. Procedure and precautions for flaring work
a.
Cut the pipe
Use a pipe cutter, and cut slowly so the pipe will not be deformed.
b.
Remove burrs and clean shavings from the cut surface
If the shape of the pipe end is poor after removing burrs, or if
shavings adhere to the flared area, it may lead to refrigerant leaks.
To prevent this, turn the cut surface downward and remove burrs,
then clean the surface, carefully.
c.
Insert the flare nut (be sure to use the same nut that is used on the
AC unit)
d.
Flaring
Check the clamp bar and the cleanliness of the copper pipe.
Be sure to use the clamp bar to do the flaring with accuracy.
Use either an R410A flaring tool, or a conventional flaring tool.
Flaring tools come in different sizes, so be sure to check the size
before using. When using a conventional flaring tool, use the
copper pipe gauge for clearance adjustment, etc., to ensure the
correct A dimension (see Fig. 10)
Fig. 10 Flaring dimensions
Fig. 11 Relation between the flare nut structure and flaring tool end
Table 11 R410A flaring dimensions
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A(mm)
R410A flaring
tool, clutch type
Conventional flaring tool
Clutch type
Wing-nut type
1/4
6.35
0.8
0 - 0.5
1.0 - 1.5
1.5 - 2.0
3/8
9.52
0.8
0 - 0.5
1.0 - 1.5
1.5 - 2.0
1/2
12.70
0.8
0 - 0.5
1.0 - 1.5
2.0 - 2.5
42
CS-VG120KE / CU-VG120KE
Содержание CS-VG120KE
Страница 3: ...2 Functions 2 1 REMOTE CONTROL 3 CS VG120KE CU VG120KE ...
Страница 4: ...2 2 INDOOR UNIT 4 CS VG120KE CU VG120KE ...
Страница 5: ...5 CS VG120KE CU VG120KE ...
Страница 6: ...2 3 OUTDOOR UNIT 6 CS VG120KE CU VG120KE ...
Страница 9: ...4 Dimensions 4 1 CS VG120KE INDOOR UNIT 9 CS VG120KE CU VG120KE ...
Страница 10: ...4 2 CU VG120KE OUTDOOR UNIT 10 CS VG120KE CU VG120KE ...
Страница 12: ...6 Block Diagram CS VG120KE CU VG120KE 12 ...
Страница 49: ...11 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 49 CS VG120KE CU VG120KE ...
Страница 62: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 62 CS VG120KE CU VG120KE ...
Страница 68: ...CS VG120KE CU VG120KE 68 ...
Страница 69: ...15 Printed Circuit Board 15 1 CS VG120KE INDOOR UNIT 69 CS VG120KE CU VG120KE ...
Страница 70: ...70 CS VG120KE CU VG120KE ...
Страница 71: ...15 2 CU VG120KE OUTDOOR UNIT POWER SUPPLY 71 CS VG120KE CU VG120KE ...
Страница 72: ...MAIN INDICATOR 72 CS VG120KE CU VG120KE ...
Страница 73: ...16 Exploded View Replacement Parts List 16 1 CS VG120KE 16 1 1 Exploded View 73 CS VG120KE CU VG120KE ...
Страница 75: ...16 2 CU VG120KE 16 2 1 Exploded View 75 CS VG120KE CU VG120KE ...
Страница 78: ...MEMO ...
Страница 79: ...MEMO ...
Страница 80: ...Printed in Japan MS1299SO ...