Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
•
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
•
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
8 Operation Details
8.1. Cooling Mode Operation
•
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
•
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
•
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
•
When the compressor outdoor fan motor and indoor fan motor are simultaneous ly started, the indoor fan motor will operate 1.6
second later.
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically .
(Time Delay Safety Control is valid)
▲
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneou s power failure.
•
Purpose is to prevent dew formation on indoor unit air discharge area.
•
When the following conditions accur for 30 minutes continuously , anti-dew formation is controlled by indoor fan speed shift to
low (CLo to HLo):
−
Indoor intake air temperature is more than 24°C and less than 30°C.
−
Remote Control setting temperature is less than 25°C.
−
Compressor is on.
−
Cooling operation mode.
−
Indoor Fan motor operate at Low fan speed.
•
This control is cancelled immediately when above condition is changed.
26
CS-V9BK PG CU-2 V14B KP5G / CS-V9BKP G CU-2 V18B KP5G / CS-V9BKP G CU-3 V20B KP5G / CS-V7BKP G CU-2 V19B KP5G / CS-V12B KPG
Содержание CS-V9BKPG
Страница 15: ...15 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 17: ...17 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 19: ...19 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 20: ...20 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 21: ...21 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 23: ...23 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 24: ...24 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 25: ...25 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 67: ...67 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 68: ...68 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...
Страница 90: ...90 CS V9BKPG CU 2V14BKP5G CS V9BKP G CU 2V18BKP5G CS V9BKP G CU 3V20BKP5G CS V7BKP G CU 2V19BKP5G CS V12BKPG...