79
16.2
Protection Control for Cooling & Soft Dry Operation
16.2.1 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor
frequency will adjust base on outdoor air temperature.
The compressor will be stopped to avoid compressor overloading.
-10°C
-12°C
COMP. ON
COMP. OFF
Outdoor
Air
Temperature
16.2.2 Cooling Overload Control
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency).
The compressor stop if outdoor pipe temperature exceeds 60°C.
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection).
16.2.3 Freeze Prevention Control 1
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
At the same time, indoor fan speed will be higher than during its normal operation.
If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal
operation.
16.2.4 Freeze Prevention Control 2
Control start conditions
o
During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
Содержание CS-TZ60TKEW
Страница 25: ...25 8 Block Diagram 8 1 Indoor Unit FUSE 301 TEMP FUSE SC U 1 2 3 M INDOOR UNIT ...
Страница 32: ...32 11 1 2 Indicator Printed Circuit Board CN DISP LED206 LED205 LED203 LED201 LED204 LED202 ...
Страница 33: ...33 11 2 Outdoor Unit CN STM1 CN MTR1 CN MTR2 CN TANK CN TH1 CN HOT AC BLK DATA AC WHT POWER TRANSISTOR IPM ...
Страница 122: ...122 19 1 5 To Remove Control Board Figure 6 19 1 6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 Figure 8 ...
Страница 123: ...123 Figure 9 Figure 10 ...