33
13.1.5.
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below.
If compressor discharge temperature exceeds 110
q
C, compressor will stop, occurs 4 times per 20 minutes, timer LED will be
blinking. (“F97” is to be confirmed.)
13.1.6.
Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.6A and 1.15A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
q
C.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5
q
C.
b. Control contents
• Compressor stops (and restart after 2 minutes).
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated.
13.1.7.
Low Frequency Protection Control 1
When the compressor operate at frequency lower than 25 Hz continued for 240 minutes, the operation frequency will be changed to
24 Hz for 2 minutes.
13.1.8.
Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (
q
C)
T < 14 or T 30
T < 14 or T 28
Outdoor air (
q
C)
T < 13 or T 38
T < 4 or T 24
Indoor heat exchanger (
q
C)
T < 30
T
0
Содержание CS-TE12HKE
Страница 8: ...8 5 Dimensions 5 1 Indoor Unit ...
Страница 9: ...9 5 2 Outdoor Unit ...
Страница 10: ...10 6 Refrigeration Cycle Diagram ...
Страница 11: ...11 7 Block Diagram ...
Страница 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 13: ...13 8 2 Outdoor Unit ...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 15: ...15 9 2 Outdoor Unit ...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Printed Circuit Board ...
Страница 17: ...17 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 20: ...20 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 43: ...43 16 1 2 Removal of Electronic Controller ...
Страница 44: ...44 16 1 3 Removal of Control Board ...
Страница 45: ...45 16 1 4 Removal of Fan Motor and Cross Flow Fan ...
Страница 46: ...46 ...
Страница 48: ...48 17 Technical Data 17 1 Operation Characteristics ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 51: ...51 ...