Deice Control
Deice operation is to protect the outdoor unit from freezing.
•
•
•
•
Normal Deice Operation
Decing starts 30 minutes after heating mode operation or 60 minutes after the latest decing operation. If temperature of
outdoor piping, tested by TRS, falls to 3°C (TRS OFF)or below for continuously 50 seconds, deicing operation starts.
•
•
•
•
Overload Deicing Operation
During heating operation, if the accumulative stopping time of outdoor fan reaches 60 minutes, deicing operation will start
1 minute after compressor starts.
•
•
•
•
Deicing operation ends under conditions below
1. After 12 minutes.
2. Temperature of outdoor unit rises to 4°C.
3. Because of time delay (Td), deicing operation will not end immediately.
•
•
•
•
Once deicing starts, it will not end within 60 seconds.
•
•
•
•
When deicing operation ends, compressor will stop for 30 seconds, and 4-way valve remains at cooling mode operation for
10 seconds.
20
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Содержание CS-SA9CKP
Страница 9: ...3 Dimensions 9 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 10: ...10 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 11: ...4 Refrigeration Cycle Diagram 11 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 12: ...5 Block Diagram 12 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 13: ...6 Wiring Diagram 13 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 17: ...Time Graph for soft dry operation 17 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 26: ...26 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 55: ...13 Exploded View CS SA9CKP CS SA12CKP 55 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 57: ...15 Exploded View CU SA9CKP5 CU SA12CKP5 57 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 61: ...17 1 REMOTE CONTROL 61 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Страница 62: ...17 2 PRINTED CIRCUIT BOARD REMOTE CONTROL 62 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5 Printed in China...