WARNING 

16.  Disassembly and Assembly Instructions 

 

 

 

High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding 
with repair work. Failure to heed this caution may result in electric shocks. 

16.1  Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor 

Removal Procedures 

16.1.1  To remove front grille 

 

 

Figure 1 

16.1.2  To remove horizontal vane 

 

 

Figure 2 

 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание CS-RE9QKE

Страница 1: ...WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical...

Страница 2: ...art Control 42 12 8 Indication Panel 42 13 Protection Control 43 13 1 Protection Control For All Operations 43 13 2 Protection Control For Cooling Soft Dry Operation 45 13 3 Protection Control For Hea...

Страница 3: ...Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Do not use joint cable for indoor outdoor connection cable Use the specified Indoor Outdoor con...

Страница 4: ...g point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to sp...

Страница 5: ...42 30 22 Indoor Noise Power Level dB 57 58 dB A 47 48 Cooling Outdoor Noise Power Level dB 62 63 kW 0 80 3 30 4 10 0 80 4 00 5 10 BTU h 2730 11300 14000 2730 13600 17400 Capacity kcal h 690 2840 3530...

Страница 6: ...moval L h Pt h 1 5 3 2 2 0 4 2 Cool m 3 min ft 3 min 5 74 203 5 69 201 QLo Heat m 3 min ft 3 min 7 03 248 6 79 240 Cool m 3 min ft 3 min 6 68 236 7 59 268 Lo Heat m 3 min ft 3 min 7 62 269 8 85 312 Co...

Страница 7: ...tion Range Heating Minimum C 15 16 15 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry B...

Страница 8: ...1 29 Indoor Noise Power Level dB 60 dB A 49 Cooling Outdoor Noise Power Level dB 64 kW 0 80 5 00 6 80 BTU h 2730 17100 23200 Capacity kcal h 690 4300 5850 Running Current A 6 00 Input Power W 200 1 35...

Страница 9: ...910 Moisture Removal L h Pt h 2 4 5 1 Cool m 3 min ft 3 min 6 94 245 QLo Heat m 3 min ft 3 min 8 17 288 Cool m 3 min ft 3 min 7 81 276 Lo Heat m 3 min ft 3 min 10 03 354 Cool m 3 min ft 3 min 10 16 35...

Страница 10: ...Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 F Dry Bulb and outdoor air te...

Страница 11: ...on substances refrigerant R410A Long Installation Piping o CS CU RE9 12 15QKE long piping up to 15 meters Easy to use remote control Quality Improvement o Random auto restart after power failure for s...

Страница 12: ...direction louver Do not adjust by hand Horizontal Airflow direction louver Manually adjust INDICATOR POWER Green TIMER Orange 4 2 Outdoor Unit 4 3 Remote Control MODE TEMP OFF ON TIMER SET CANCEL ON O...

Страница 13: ...Control Remote Control Holder 22 47 134 61 51 870 1 2 1 2 214 61 45 Right piping hole 290 214 125 115 60 60 410 41 61 Gas side Liquid side Relative position between the indoor unit and the installati...

Страница 14: ...e View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100 mm 100 mm 1000 mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 69 6 18 61 6 542...

Страница 15: ...w Side View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100mm 100mm 1000mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 22 124 62 6 33...

Страница 16: ...SOR PIPE TEMP SENSOR 2 COMPRESSOR TEMP SENSOR PIPE TEMP SENSOR 1 PIPE TEMP SENSOR OUTDOOR AIR TEMP SENSOR LIQUID SIDE 2 WAY VALVE 3 WAY VALVE GAS SIDE COOLING HEAT EXCHANGER EVAPORATOR HEATING COMPRES...

Страница 17: ...FUSE101 FUSE104 REACTOR FUSE102 RY PWR PTC1 PTC NTC TH3 CT102 4 WAYS VALVE RY AC FUSE103 IC19 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N SINGLE PH...

Страница 18: ...1 FUSE101 FUSE104 REACTOR FUSE102 RY PWR PTC1 PTC NTC TH3 CT102 4 WAYS VALVE RY AC FUSE103 P N IC20 Q1 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N S...

Страница 19: ...PLY 1 230V 50Hz ELECTRONIC CONTROLLER MAIN UP DOWN LOUVER MOTOR CN STM1 WHT BR 1 5 1 5 R O M Y P REMARKS B BLUE P PINK BR BROWN O ORANGE BL BLACK Y YELLOW W WHITE G GREEN R RED Y G YELLOW GREEN CN DIS...

Страница 20: ...YS VALVE 1 3 CN HOT WHT CN TH WHT P N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 FUSE104 15...

Страница 21: ...E 1 3 CN HOT WHT CN TH WHT P N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V...

Страница 22: ...e Temp Sensor Intake Air Temp Sensor 1 1 2 2 CN DISP YELLOW UP DOWN LOUVER MOTOR CN STM1 WHITE 1 5 4 3 2 12V 74 144 70 64 61 M 12V 1 2 3 4 5 6 7 16 9 8 15 14 13 12 11 10 IC03 R47 1 2W 68 5 143 R46 1 2...

Страница 23: ...N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 RED 2 WHITE S1 BLACK COMMUNICATION CIRCUIT PFC CIRCUIT W U V ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT...

Страница 24: ...WER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 RED 2 WHITE S1 BLACK COMMUNICATION CIRCUIT PFC CIRCUIT W U V ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT RECTIFICATION C...

Страница 25: ...25 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board CN FM CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 JP1 Random Auto Restart enable disable...

Страница 26: ...26 10 1 2 Indicator Receiver Printed Circuit Board CN DISP...

Страница 27: ...27 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE9QKE CN HOT CN STM CN TH CN MTR1 CN MTR2 CN TANK AC BLK DATA AC WHT POWER TRANSISTOR IPM CURRENT TRANSFORMER CT...

Страница 28: ...28 10 2 1 2 CU RE12QKE CU RE15QKE CN HOT CN MTR1 CN MTR2 CN TH CN STM CN TANK AC BLK DATA AC WHT POWER TRANSISTOR IPM CURRENT TRANSFORMER CT...

Страница 29: ...1 4 5 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 10 30 30 3 20 P H 5 1 2 1 E Y 2 1 E U 2 1 E R RE15 1 75HP 12 7mm 1 2 UE18 2 0HP 7 5 20 20 3 15 8 1 E R RE24 2 5HP 15 88mm 5 8 Example...

Страница 30: ...ith 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts o Always mount the installation plate horizontally by aligning the marking off line with th...

Страница 31: ...necting the piping column in outdoor unit section Below steps are done after connecting the outdoor piping and gas leakage confirmation Step 7 Insulate and finish the piping Step 8 Secure the Indoor U...

Страница 32: ...Isolating Devices Disconnecting means o Connect approved type polychloroprene sheathed power supply cord 3 1 5 mm2 1 0 1 75HP 3 2 5 mm2 2 0 2 5HP type designation 60245 IEC 57 or heavier cord to the t...

Страница 33: ...ew and close the front panel Recommended length mm Tape Connection cable Tape Power supply cord Recommended length mm a 55 b 35 c 35 d 50 e 40 f 35 g 60 Terminal Board Control Board Earth wire longer...

Страница 34: ...NG REQUIREMENT Conductor fully inserted Conductor not fully inserted gap between wires WARNING RISK OF FIRE JOINING OF WIRES MAY CAUSE OVERHEATING AND FIRE Do not joint wires OR OR OR Use complete wir...

Страница 35: ...at joint portion of tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten t...

Страница 36: ...e that the needle in the gauge does not move after approximately five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE 5 Disconnect the charging hose from the vacu...

Страница 37: ...ly earthed Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for safety reason 11 3 5 Piping Insulation 1 Please carry out insulation at pipe connection portion as mentione...

Страница 38: ...ting temperature and it is updated continuously whenever the electrical power is supplied to the unit 12 1 2 Cooling Operation 12 1 2 1 Thermostat control Compressor is OFF when Intake Air Temperature...

Страница 39: ...3 C if previous operate in DRY mode then continue in DRY mode otherwise COOL mode is decided o If 2 C indoor intake temperature remote control setting temperature 3 C maintain with previous mode o If...

Страница 40: ...then H19 fan motor error is detected Operation stops and cannot on back 12 3 Outdoor Fan Motor Operation Outdoor fan motor is operated with one fan speed only It starts when compressor starts operatio...

Страница 41: ...e For heating mode operation the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below It does not swing during fan motor stop When the air conditioner is stopped using...

Страница 42: ...be selected randomly after power supply resumes This type of control is not applicable during ON OFF Timer setting This control can be omitted by open the circuit of JP1 at indoor unit printed circui...

Страница 43: ...oft Dry A 4 41 6 07 7 94 Cooling Soft Dry B 3 94 5 52 7 42 Cooling Soft Dry C 3 94 5 52 7 42 Heating 4 65 15 02 6 00 15 02 9 13 15 02 4 The first 30 minutes of cooling operation A will be applied 13 1...

Страница 44: ...nd Soft Dry operations Indoor suction temperature indoor piping temperature is below 4 C o During Heating operations Indoor piping temperature indoor suction is under 5 C Control contents o Compressor...

Страница 45: ...anger is higher than 5 C At the same time indoor fan speed will be higher than during its normal operation If indoor heat exchanger temperature is higher than 5 C for 5 minutes the fan speed will retu...

Страница 46: ...13 3 2 Outdoor Air Temperature Control The Max current value is regulated when the outdoor air temperature rise above 14 C in order to avoid compressor overloading 13 3 3 Overload Protection Control T...

Страница 47: ...NTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11th seconds to...

Страница 48: ...ote Control Receiving Sound OFF ON Mode is restarted 14 2 Remote Control Button 14 2 1 SET Button To check remote control transmission code and store the transmission code to EEPROM o Press Set button...

Страница 49: ...problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature a...

Страница 50: ...lectric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit H...

Страница 51: ...ly for 5 seconds 3 will be displayed on the remote controller display Note Display only for No transmitting signal no receiving sound and no Power LED blinking 4 Press the TIMER or button on the remot...

Страница 52: ...lity Port is ON for 10s during ion device off ion device PCB H27 Outdoor air temperature sensor abnormality Continuous for 5s Outdoor air temperature sensor open or short circuit Outdoor air temperatu...

Страница 53: ...ing abnormality 3 times happen within 40 minutes Wrong wiring and connecting pipe expansion valve leakage indoor heat exchanger sensor open circuit Check indoor outdoor connection wire and pipe Indoor...

Страница 54: ...ved from outdoor unit in indoor unit signal transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission...

Страница 55: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 56: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 57: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Страница 58: ...on Conditions An input current detected by Current Transformer CT is below threshold value when the compressor is operating at certain frequency value for 3 minutes Malfunction Caused Lack of gas Brok...

Страница 59: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Страница 60: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 61: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 62: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Страница 63: ...ion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction C...

Страница 64: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors Malfunction...

Страница 65: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Страница 66: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 67: ...ecision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors Malfunction Caused Fault...

Страница 68: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors Malfunction Cau...

Страница 69: ...pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation Phenomena unit is stopping and re starting very often in heating mod...

Страница 70: ...ecision Conditions Freeze prevention control takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit he...

Страница 71: ...old during heating except deice or when indoor heat exchanger is hot during cooling and compressor operating the 4 way valve is detected as malfunction Malfunction Caused Indoor heat exchanger pipe th...

Страница 72: ...ature and indoor pipe temperature is above 10 C or indoor pipe temperature is below 1 0 C Remark When the indoor standby unit is freezing the outdoor unit transfers F17 error code to the corresponding...

Страница 73: ...tartup and operation of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors When DC voltage de...

Страница 74: ...igeration Cycle Abnormality Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency Malfunction Caused Lack of gas 3 way valve clo...

Страница 75: ...lfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disco...

Страница 76: ...the outdoor unit heat exchanger thermistor Malfunction Caused Outdoor heat exchanger temperature rise due to short circuit of hot discharge air flow Outdoor heat exchanger temperature rise due to defe...

Страница 77: ...ated o Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short...

Страница 78: ...n of cooling and heating when compressor tank temperature data 103 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve clo...

Страница 79: ...urrent Control is detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over curre...

Страница 80: ...t peak due to short circuit Troubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a l...

Страница 81: ...or Ensure that the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 16 1 Indoor Electronic Controllers Cross Flow Fan...

Страница 82: ...M CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 Figure 3 Figure 4 16 1 4 To remove discharge grille 10 Pull out to remove the drain hose from the discharge grille 11 Then pull the disch...

Страница 83: ...oard then pull out the control board Figure 6 16 1 6 To remove cross flow fan and indoor fan motor 13 Remove the screw that holding the cross flow fan and fan motor axis Figure 7 15 Remove the bearing...

Страница 84: ...fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 17 Remove the cross flow fan from the unit by pulling it to the left and downward E...

Страница 85: ...controller be careful of electrostatic discharge 1 Remove the 3 screws of the Top Panel Fig 1 2 Remove the 6 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove th...

Страница 86: ...l of electrostatic discharge 1 Remove the 5 screws of the Top Panel Fig 1 2 Remove the 8 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove the Top Cover of the Co...

Страница 87: ...0 2948 1000 27 22 0 3691 2223 582 3536 2123 657 3802 2222 570 3538 2123 638 4397 2478 667 4047 2339 827 3669 1750 1013 15 7 2901 2619 656 2926 2657 657 2869 2601 656 3005 2772 580 3558 3064 660 3248 2...

Страница 88: ...KE CU RE12QKE Indoor C Outdoor WB C 15 7 2 7 12 DB TC IP TC IP TC IP TC IP TC IP 24 2379 1099 3290 1434 3647 1314 3702 1110 4074 1183 20 2449 1059 3300 1380 3700 1260 4000 1050 4237 1135 16 2287 1012...

Страница 89: ...ed cooling at 16 C Hi fan Compressor frequency Rated for cooling operation Piping length 5m Voltage 230V 18 1 1 CS CU RE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C Low Pressure MPa Outdoo...

Страница 90: ...re MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 2 00 2 40 2 80 3 20 3 60 4 00 4 40 4 80 5 20 12 16 20 24 28 32 36 40 44 48 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 12 16 20 24 28 3...

Страница 91: ...ure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 1 50 2 50 3 50 4 50 5 50 6 50 7 50 12 16 20 24 28 32 36 40 44 48 0 60 0 70 0 80 0 90 1 00 1 10 12 16 20 24 28 32 36 40 44 48 12 00...

Страница 92: ...ompressor frequency Rated for Heating operation Piping length 5m Voltage 230V 18 2 1 CS CU RE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C High Pressure MPa Outdoor Air Temperature C Curren...

Страница 93: ...igh Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 20 24 28 32 36 40 44 20 15 10 5 0 5 10 15 2 70 2 90 3 10 3 30 3 50 3 70 3 90 4 10 4 30 4 50 4 70 4 90 5 10 20 15 10 5 0 5...

Страница 94: ...Temperature C High Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 4 00 4 50 5 00 5 50 6 00 6 50 7 00 20 15 10 5 0 5 10 15 1 80 2 00 2 20 2 40 2 60 2 80 3 00 3 20 3 40 3 60...

Страница 95: ...CU RE12QKE CS CU RE15QKE 0 92 0 94 0 96 0 98 1 00 1 02 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Cooling Capacity Correction Factor Heating Capacity Correction Factor Pipe Length m 0 90 0 92 0 94 0 96 0 9...

Страница 96: ...36 33 45 62 57 58 59 60 61 I I I I I I I I I I O I 46 47 48 54 55 56 40 3 4 2 5 1 27 23 11 16 26 34 28 29 30 39 9 37 35 7 38 8 41 42 43 50 53 52 51 44 10 49 Note The above exploded view is for the pur...

Страница 97: ...28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521259 35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 36 REMOTE CON...

Страница 98: ...K 59 INSTALLATION INSTRUCTION 1 CWF616278 60 INSTALLATION INSTRUCTION 1 CWF616279 61 INSTALLATION INSTRUCTION 1 CWF616280 62 OPERATING INSTRUCTION 1 CWF569460 NOTE All parts are supplied from PAPAMY M...

Страница 99: ...30 17 16 10 11 4 12 22 21 19 26 25 38 39 9 2 1 23A 43 42 23B 31 35 33 20 14 24 29 47 55 53 54 51 52 50 23C 41 13 8 Note The above exploded view is for the purpose of parts disassembly and replacement...

Страница 100: ...ND PROOF BOARD 1 CWH151172 23A SOUND PROOF MATERIAL 1 CWG302315 23B SOUND PROOF MATERIAL 1 CWG302316 23C SOUND PROOF MATERIAL 1 CWG302317 24 SENSOR CO COMP TEMP 1 CWA50C2205 O 25 CONTROL BOARD COVER T...

Страница 101: ...RT NAME DESCRIPTION QTY CU RE9QKE REMARK 54 SHOCK ABSORBER LEFT 1 CWG712970 55 C C CASE 1 CWG568357 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended...

Страница 102: ...39 21 20 9 31 11 10 15 1 16 17 4 23A 23B 23C 22 2 3 8 7 5 30 12 24 29 41 13 6 47 46 48 49 50 25 14 43 42 45 Note The above exploded view is for the purpose of parts disassembly and replacement The no...

Страница 103: ...CWH7080300J 22 SOUND PROOF BOARD 1 CWH151274 23A SOUND PROOF MATERIAL 1 CWG302317 23B SOUND PROOF MATERIAL 1 CWG302701 23C SOUND PROOF MATERIAL 1 CWG302726 24 SENSOR CO COMP TEMP 1 CWA50C2894 o 25 CON...

Страница 104: ...CU RE12QKE CU RE15QKE REMARK 49 SHOCK ABSORBER LEFT 1 CWG713416 50 C C CASE 1 CWG566848 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept...