42
12.6 OFF Timer Control
OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
12.7 Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
12.8 Indication Panel
LED POWER
TIMER
Color Green Orange
Light ON
Operation ON
Timer Setting ON
Light OFF
Operation OFF Timer
Setting
OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.