14.4.12    H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) 

Malfunction Decision Conditions 

  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) 

 

Malfunction Caused 

  Clogged air filter of the indoor unit 

  Dust accumulation on the indoor unit heat exchanger 

  Air short circuit 

  Detection error due to faulty indoor pipe temperature sensor 

  Detection error due to faulty indoor unit PCB 

 

Troubleshooting 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание CS-PS9NKV

Страница 1: ...se by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be...

Страница 2: ...trol 49 11 6 Random Auto Restart Control 50 11 7 Indication Panel 50 12 Protection Control 51 12 1 Restart Control Time Delay Safety Control 51 12 2 30 Seconds Forced Operation 51 12 3 Total Running C...

Страница 3: ...ire 9 This equipment is strongly recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakd...

Страница 4: ...5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a...

Страница 5: ...Hermetic Motor Rotary Hermetic Motor Rotary Motor Type Brushless 6 poles Brushless 6 poles Compressor Output Power W 650 650 Type Cross flow fan Cross flow fan Material ASG20K1 ASG20K1 Motor Type Ind...

Страница 6: ...coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 15 x 17 2 x 15 x 17 Indoor Heat Exchanger Size W x H x L mm 610 x 315 x 25 4 610 x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue...

Страница 7: ...Cross flow fan Material ASG30K1 ASG30K1 Motor Type Transistor 8 poles Transistor 8 poles Input Power W 94 8 94 8 Output Power W 40 40 Lo rpm 930 960 Me rpm 1110 1140 Indoor Fan Speed Hi rpm 1300 1330...

Страница 8: ...x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 24 x 17 1 x 31 x 19 Outdoor Heat Exchanger Size W x H x L mm 25 4 x 504 x 693 4...

Страница 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...

Страница 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9NKV CS PS12NKV...

Страница 11: ...11 4 1 2 CS PS18NKV CS PS24NKV...

Страница 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9NKV 4 2 2 CU PS12NKV CU PS18NKV...

Страница 13: ...13 4 2 3 CU PS24NKV...

Страница 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9NKV CU PS9NKV CS PS12NKV CU PS12NKV...

Страница 15: ...15 5 2 CS PS18NKV CU PS18NKV CS PS24NKV CU PS24NKV...

Страница 16: ...16 6 Block Diagram 6 1 CS PS9NKV CU PS9NKV...

Страница 17: ...17 6 2 CS PS12NKV CU PS12NKV...

Страница 18: ...18 6 3 CS PS18NKV CU PS18NKV...

Страница 19: ...19 6 4 CS PS24NKV CU PS24NKV...

Страница 20: ...20 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS PS9NKV CS PS12NKV...

Страница 21: ...21 7 1 2 CS PS18NKV CS PS24NKV...

Страница 22: ...22 7 2 Outdoor Unit 7 2 1 CU PS9NKV Resistance of Compressor Windings MODEL CU PS9NKV CONNECTION 5RS092XCE21 U V 1 152 U W 1 152 V W 1 152...

Страница 23: ...23 7 2 2 CU PS12NKV Resistance of Compressor Windings MODEL CU PS12NKV CONNECTION 5RS092XCD21 U V 1 152 U W 1 152 V W 1 152...

Страница 24: ...24 7 2 3 CU PS18NKV Resistance of Compressor Windings MODEL CU PS18NKV CONNECTION 5RD132XDA21 U V 1 152 U W 1 152 V W 1 152...

Страница 25: ...25 7 2 4 CU PS24NKV Resistance of Compressor Windings MODEL CU PS24NKV CONNECTION 5RD132XBA21 U V 1 897 U W 1 907 V W 1 882...

Страница 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9NKV CS PS12NKV...

Страница 27: ...27 8 1 2 CS PS18NKV CS PS24NKV...

Страница 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9NKV...

Страница 29: ...29 8 2 2 CU PS12NKV...

Страница 30: ...30 8 2 3 CU PS18NKV...

Страница 31: ...31 8 2 4 CU PS24NKV...

Страница 32: ...32 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board 9 1 1 1 CS PS9NKV CS PS12NKV...

Страница 33: ...33 9 1 1 2 CS PS18NKV CS PS24NKV 9 1 2 Indicator and Receiver Printed Circuit Board...

Страница 34: ...34 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9NKV...

Страница 35: ...35 9 2 1 2 CU PS12NKV...

Страница 36: ...36 9 2 1 3 CU PS18NKV...

Страница 37: ...37 9 2 1 4 CU PS24NKV...

Страница 38: ...38 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9NKV...

Страница 39: ...ed installation height for indoor unit shall be at least 2 5 m 10 1 2 Outdoor Unit If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the conden...

Страница 40: ...ts o Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Line according...

Страница 41: ...2 3 Indoor Unit Installation 10 2 3 1 For the right rear piping 10 2 3 2 For the right and right bottom piping 10 2 3 3 For the embedded piping This can be used for left rear piping and bottom piping...

Страница 42: ...indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 5 mm2 1 0 1 5HP or 4 x 2 5 mm2 2 0 2 5HP flexible cord type designation 245 IEC 57 or heavier cord Do not use joint conne...

Страница 43: ...hown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage 10 2 5 Wire Stripping And Connecting Requirement 10 2 6 Cutting and flaring the piping 1 Please...

Страница 44: ...f tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with t...

Страница 45: ...g 0 MPa to 76 cmHg 0 1 MPa Then evacuate the air approximately ten minutes 4 Close the Low side valve of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not m...

Страница 46: ...board with the holder clamper 4 Attach the control board cover back to the original position with the screw 5 For wire stripping and connection requirement refer to instruction 10 2 4 of the indoor u...

Страница 47: ...2 Cooling Operation 11 1 2 1 Thermostat control Compressor is OFF when intake Air Temperature Internal Setting Temperature 0 5 C Compressor is ON after waiting for 3 minutes if the Intake Temperature...

Страница 48: ...ately after the fan motor is started feedback control is performed once every second o During fan motor on if fan motor feedback 2550 rpm or 50 rpm continuously for 10 seconds the fan motor error coun...

Страница 49: ...rol the vane will shift to close position Manual vertical airflow direction can be set using remote control the angles of the vane are as stated above and the positions of the vane are as figure below...

Страница 50: ...the power supply is cut off during the operation of air conditioner the compressor will re operate within three to four minutes There are 10 patterns to be selected randomly after power supply resumes...

Страница 51: ...creased If the running current does not exceed X value for 5 seconds the frequency instructed will be increased However if total outdoor unit running current exceeds Y value compressor will be stopped...

Страница 52: ...s 30 5 C Remote Control setting 16 C and Hi Fan Speed Control contents o Compressor stops and restart after 3 minutes o If the conditions above happened 2 times within 20 minutes the unit will Stop op...

Страница 53: ...or Compressor stops for freeze prevention control o Either one of the conditions above occurs 5 times in 60 minutes Control contents o Operation stops o Timer LED blinks and H99 indicated 12 13 Dew P...

Страница 54: ...ld be selected The indoor unit will only operate when received signal with same transmission code from remote control This could prevent signal interference when there are 2 or more units installed ne...

Страница 55: ...on unit a beep sound is heard as confirmation of transmission code change 13 2 2 RESET RC Button To clear and restore the remote control setting to factory default o Press once to clear the memory 13...

Страница 56: ...Mpa kg cm 2 G Outlet air Temperature C Cooling Mode 0 9 1 2 9 12 12 16 Condition Indoor fan speed High Outdoor temperature 35 C at cooling mode Compressor operate at rated frequency Different in the i...

Страница 57: ...w Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or strainer Short circuit in the indoor unit Heat radiation deficiency of the out...

Страница 58: ...2 3 To Display Memorized Error Code Protective Operation 1 Turn power on 2 Press the CHECK button on the remote control 3 will be displayed on the remote control display Note Display only for No sign...

Страница 59: ...ir filter dirty Air circulation short circuit H99 Indoor heat exchanger freeze prevention protection Insufficient refrigerant Air filter dirty F11 4 way valve switching failure 4 occurrences within 30...

Страница 60: ...transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdo...

Страница 61: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 62: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 63: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Страница 64: ...ons A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 1 14A for continuously 20 seconds Malfunction Caused CT de...

Страница 65: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Страница 66: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 67: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 68: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Страница 69: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Страница 70: ...uring heating operation the temperature detected by the indoor pipe temperature sensor is above 60 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat...

Страница 71: ...n control takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Dete...

Страница 72: ...unction Decision Conditions When cooling operation when indoor pipe temperature or indoor heat exchanger temperature sensor is above 45 C Malfunction Caused Faulty connector connection Faulty indoor p...

Страница 73: ...eration of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power...

Страница 74: ...cooling and heating operation running current 0 65A I 1 65A During cooling indoor intake indoor pipe 4 C Malfunction Caused Refrigerant shortage refrigerant leakage Poor compression performance of com...

Страница 75: ...lfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disco...

Страница 76: ...detected by the outdoor pipe temperature sensor Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow Outdoor pipe temperature rise due to defective of outdo...

Страница 77: ...ture data 100 C is detected by the IPM temperature sensor Malfunction Caused IPM overheats due to short circuit of hot discharge air flow IPM overheats due to defective of outdoor fan motor IPM overhe...

Страница 78: ...n of cooling and heating when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve clo...

Страница 79: ...rent Control is detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over current...

Страница 80: ...door unit PCB Troubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a live part make...

Страница 81: ...the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 15 1 CS PS9 12NKV 15 1 1 Indoor Electronic Controllers Cross Fl...

Страница 82: ...82 Figure 3 Figure 4 15 1 3 To remove discharge grille Figure 5 10 Pull out to remove the drain hose from the discharge grille 11 Then pull the discharge grille downward gently to dismantle it...

Страница 83: ...and indoor fan motor Figure 7 Figure 8 12 Remove 4 screws holding the control board then pull out the control board 15 Remove the bearing by pulling it out gently 14 Remove the screw from the evapora...

Страница 84: ...val of cross flow fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 17 Remove the cross flow fan from the unit by pulling it to the l...

Страница 85: ...charged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 15 2 CS PS18 24NKV 15 2 1 Indoor Electronic Controllers Cross Flow Fan and Indoor Fan...

Страница 86: ...86 Figure 13 Figure 14 15 2 3 To remove discharge grille Figure 15...

Страница 87: ...87 15 2 4 To remove control board Figure 16 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18...

Страница 88: ...88 Figure 19 Figure 20...

Страница 89: ...16 100 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outlet Air Tempeature C Outdoor Air Temperature C 220 2 100 2 200 2 300 2 400 2 500 2 600 2 700 2 800 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor...

Страница 90: ...3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 3 300 3 350 3 400 3 450 3 4 5 6 7 8 9 10 11 12 13 14 15 Current A Piping Length m 1 140 1 142 1 144 1 146 1 148 1 150 1 152 1 154 3...

Страница 91: ...1 42 43 Outlet Air Tempeature C Outdoor Air Temperature C 220 2 600 2 700 2 800 2 900 3 000 3 100 3 200 3 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 3...

Страница 92: ...100 3 200 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 3 900 3 950 4 000 4 050 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Current A 1 080 1 085 1 090 1 095 1 100 3 4 5 6 7...

Страница 93: ...9 40 41 42 43 Outlet Air Tempeature C Outdoor Air Temperature C 220 4 600 4 800 5 000 5 200 5 400 5 600 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 6 100 6...

Страница 94: ...16 17 18 19 20 Piping Length m Cooling Capacity kW 6 600 6 700 6 800 6 900 7 000 7 100 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Current A 0 970 0 975 0 980 0 985 0 990 0 995 3 4...

Страница 95: ...38 39 40 41 42 43 Outlet Air Tempeature C Outdoor Air Temperature C 220 5 300 5 500 5 700 5 900 6 100 6 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 7 5...

Страница 96: ...16 17 18 19 20 Piping Length m Cooling Capacity kW 8 000 8 100 8 200 8 300 8 400 8 500 8 600 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Current A 0 890 0 895 0 900 0 905 0 910 0 91...

Страница 97: ...and Replacement Parts List 17 1 Indoor Unit 17 1 1 CS PS9NKV CS PS12NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as sta...

Страница 98: ...LE COMPLETE 1 CWE20C3236 27 BACK COVER CHASSIS 1 CWD933233 28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521...

Страница 99: ...99 17 1 2 CS PS18NKV CS PS24NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 100: ...TE 1 CWE20C3243 27 BACK COVER CHASSIS 1 CWD933031 28 FULCRUM 2 CWH621138 29 VERTICAL VANE 11 CWE241374 30 CONNECTING BAR 1 CWE261260 31 CONNECTING BAR 1 CWE261263 33 AIR SWING MOTOR 1 CWA981241 O 34 C...

Страница 101: ...101 17 2 Outdoor Unit 17 2 1 CU PS9NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 102: ...H151185 20 TERMINAL COVER 1 CWH171039A 21 NUT TERMINAL COVER 1 CWH7080300J 22 SENSOR COMPLETE 1 CWA50C2205 O 23 WIRE NET 1 CWD041057A 24 SENSOR COMPLETE 1 CWA50C2502 O 25 TERMINAL BOARD ASSY 1 CWA28K1...

Страница 103: ...103 17 2 2 CU PS12NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 104: ...OVER 1 CWH171039A 21 NUT TERMINAL COVER 1 CWH7080300J 22 SENSOR COMPLETE 1 CWA50C2205 O 24 SENSOR COMPLETE 1 CWA50C2764 O 25 TERMINAL BOARD ASSY 1 CWA28K1036J O 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C6...

Страница 105: ...105 17 2 3 CU PS18NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 106: ...CWA50C2205 O 24 SENSOR CO OUTDOOR AIR HEAT EXCHANGE TEMP 1 CWA50C2764 O 25 TERMINAL BOARD ASSY 1 CWA28K1036J O 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C6346R O 28 CONTROL BOARD COVER TOP 1 CWH131264 29 C...

Страница 107: ...107 17 2 4 CU PS24NKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service part...

Страница 108: ...OUTDOOR COMP TEMP 1 CWA50C2185 23 WIRE NET 1 CWD041155A 27 SENSOR CO 1 CWA50C2769 O 28 REACTOR 1 G0C153J00005 29 TERMINAL BOARD ASSY 1 CWA28K1036J 30 ELECTRONIC CONTROLLER MAIN 1 CWA73C6347R O 31 CON...