67
RPM shift
+0
+20
+40
+70
(ID temp) Pipe
6.0°C
4.0°C
2.0°C
5.0°C
7.0°C
3.0°C
Compressor starts for
≥
5 minutes
▲
T
≤
2.5°C for 2 minutes
Compressor
OFF
Compressor
restart
▲
T = Intake air temperature – Indoor heat exchanger temperature
(For PC9/12QKH)
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed
will be increased according to the indoor pipe temperature the figure below:
14.6 Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuously 2 minutes, compressor will stop and restart
automatically.
Time Delay Safety Control is activated before the compressor restart.
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turns OFF with TIMER indicator
blinks.
The 5 Times counter can be reset when either one of the following condition happen:
o
Unit is OFF by remote control or AUTO OFF/ON button.
o
Indoor intake temperature – Indoor piping temperature > 5°C for 1 minute or more.
o
Operation mode change.
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
TIMER LED blinking will be reset if:
o
Indoor intake temperature – Indoor piping temperature > 5°C for 1 minute or more.
o
Power supply reset.
14.7 Dew Prevention Control
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o
Cooling
mode.
o
Remote Control setting temperature is less than 25°C.
o
Fan speed is at CLo.
o
Room temperature is constant (±1°C) for 60 minutes (For 9/12QKH series) and 30 minutes (For
18/24/28QKH series).
o
Compressor is continuously running.
Fan speed will be adjusted accordingly in this control.
o
Fan speed will be increased slowly.
Dew prevention stop condition
o
Remote control setting temperature is more than 25°C.
o
Fan speed is not set to CLo.
Содержание CS-PC12QKH
Страница 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS PC9QKH CS PC12QKH ...
Страница 18: ...18 5 1 2 CS PC18QKH CS PC24QKH CS PC28QKH ...
Страница 19: ...19 5 2 Outdoor Unit 5 2 1 CU PC9QKH CU PC12QKH 5 2 2 CU PC18QKH ...
Страница 20: ...20 5 2 3 CU PC24QKH 5 2 4 CU PC28QKH ...
Страница 21: ...21 6 Refrigeration Cycle Diagram ...
Страница 22: ...22 7 Block Diagram 7 1 CS PC9QKH CU PC9QKH CS PC12QKH CU PC12QKH CS PC18QKH CU PC18QKH ...
Страница 23: ...23 7 2 CS PC24QKH CU PC24QKH ...
Страница 24: ...24 7 3 CS PC28QKH CU PC28QKH ...
Страница 29: ...29 9 Electronic Circuit Diagram 9 1 CS PC9QKH CU PC9QKH CS PC12QKH CU PC12QKH ...
Страница 30: ...30 9 2 CS PC18QKH CU PC18QKH ...
Страница 31: ...31 9 3 CS PC24QKH CU PC24QKH ...
Страница 32: ...32 9 4 CS PC28QKH CU PC28QKH ...
Страница 33: ...33 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS PC9QKH CS PC12QKH ...
Страница 34: ...34 10 1 1 2 CS PC18QKH ...
Страница 35: ...35 10 1 1 3 CS PC24QKH ...
Страница 36: ...36 10 1 1 4 CS PC28QKH ...
Страница 52: ...52 12 2 5 Wire Stripping and Connecting Requirement ...
Страница 58: ...58 13 1 2 Cooling Operation Time Diagram For PC18 24 28QKH ...
Страница 60: ...60 13 2 2 Soft Dry Operation Time Diagram For PC18 24 28QKH ...
Страница 73: ...73 17 1 1 3 To Remove Discharge Grille ...
Страница 74: ...74 17 1 1 4 To Remove Control Board 17 1 1 5 To Remove Cross Flow Fan and Indoor Fan Motor ...
Страница 75: ...75 ...
Страница 77: ...77 17 2 1 3 To Remove Main Electronic Controller Fig 3 ...
Страница 78: ...78 17 2 1 4 To Remove Discharge Grille Fig 6 17 2 1 5 To Remove Control Board Fig 7 ...
Страница 79: ...79 17 2 1 6 To Remove Cross Flow Fan and Indoor Fan Motor Fig 8 Fig 9 ...
Страница 80: ...80 Fig 10 Fig 11 ...
Страница 81: ...81 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...