![Panasonic cs-pa7dkd Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/panasonic/cs-pa7dkd/cs-pa7dkd_service-manual_1507876043.webp)
4. Indoor unit installation
• Hook the indoor unit onto the upper portion of
installation plate. (Engage the two hooks of the rear top
of the indoor unit with the upper edge of the installation
plate.)
• Ensure the hooks are properly seated on the installation
plate by moving it left and right.
5. Connecting the piping to the indoor unit
• Align the center of the piping and sufficiently tighten the
flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the
wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows arrow on the
wrench.
Model
Piping side
Torque
Liquid side 1
4"
Gas side 3/8”
18N.m
42N.m
6. Set the piping and the connecting cable to the back of
chassis with the clamping cover.
7. Tape the piping, drain hose and connecting cable.
43
Fig.21
Fig.22
Fig.23
Fig.24
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD
PA7DKD
PA9DKD
PC7DKD
PC9DKD
Piping
Drain hose
Sleeve for
piping hole
Hook at
installation plate
Drain hose
Piping
Tape
Indoor unit piping
Flare Nut
Pipings
Spanner or
wrench
Torque wrench