[Heating]
According to indoor pipe temperature, automatic heating fan speed is determined as follows.
B. Feedback control
Immediately after the fan motor started, feedback control is performed once every second.
During fan motor on, if fan motor feedback
≥
2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan
motor error is detected. Operation stops and cannot on back.
14.3 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
14.3.1 Vertical
Airflow
Operation Mode
Airflow Direction
Inner Vane Angle (°)
Outer Vane Angle (°)
1 2 3 4 5 1 2 3 4 5
Cooling
Auto
110 ~ 65
50 ~ 85
Manual
110 110 90 70 65 53 62 72 83 85
Soft Dry
Auto
110 ~ 65
50 ~ 85
Manual
110 110 90 70 65 53 62 72 83 85
Heating
Auto
A 110
50
B 90
83
C 110
62
Manual
110 110 100 90 80 53 62 72 83 90
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is
stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
58°C
50°C
Indoor Heat
Exchanger Temperature
37°C
30°C
C
A
Figure 1
B