background image

11

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since 

fl

 ammability is a consideration. 

The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to 

fi

 ll until the working pressure is 

achieved, then venting to atmosphere, and 

fi

 nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the 

fi

 nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN =  oxygen free nitrogen, type of 

inert gas.

 

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant. 

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over 

fi

 ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on 

completion of charging but prior to 
commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid 

fi

 re 

or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

 

Содержание CS-MTZ16ZKE

Страница 1: ...ZKE CU RZ35ZKE CU RZ50ZKE Multi Split CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE CU 4Z80TBE CU 5Z90TBE CU 2TZ41TBE CU 2TZ50TBE CU 3TZ52TBE nanoeX ENGLISH Before operating the un...

Страница 2: ...3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press CLOCK then press to set the time Press CLOCK for approximately 5 seconds to show t...

Страница 3: ...nation purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operat...

Страница 4: ...st to clean the internal parts repair install remove disassemble and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or s...

Страница 5: ...ical shock or fire Prevent electric shock by switching off the power supply and unplug Before cleaning or servicing When extended non use or During abnormally strong lightning activity CAUTION Indoor...

Страница 6: ...working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrigera...

Страница 7: ...onmental effects such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris h Expansion and contraction of long runs piping in refrigerating systems sha...

Страница 8: ...nition and hot metal surfaces away 2 3 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is awar...

Страница 9: ...ode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks...

Страница 10: ...in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall al...

Страница 11: ...e pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available OFN oxygen free nitrogen type of inert gas 9...

Страница 12: ...rdous condition when charging or discharging the refrigerant To avoid fire or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging d...

Страница 13: ...cuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppl...

Страница 14: ...llow the remote control setting If nanoe X is activated before the unit is turned off the nanoe X operation will resume when the unit is turned on This includes when TIMER ON is set Press the button a...

Страница 15: ...ll modes Cannot be selected at the same time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the activation...

Страница 16: ...art automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set To Learn More Single Single split system Multi Multi split system Operation mode I...

Страница 17: ...43 109 4 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 16 3 2 15 5 0 16 3 2 DBT Dry bulb temperature WBT Wet bulb tem...

Страница 18: ...rings etc Wipe the unit gently with a soft damp cloth The coils and fans should be cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage...

Страница 19: ...n room temperature increase Indoor fan stops occasionally during heating operation To avoid unintended cooling effect Indoor fan stops occasionally during automatic fan speed setting This is to help r...

Страница 20: ...rly Remote control does not work Display is dim or transmission signal is weak Insert the batteries correctly Replace weak batteries The unit does not work Check if the circuit breaker is tripped Chec...

Страница 21: ...nts Use AUTO OFF ON on the unit to select COOL or HEAT mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the f...

Страница 22: ...35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand cod...

Страница 23: ...ly valid in the European Union If you wish to discard these items please contact your local authority or dealer and ask for the correct method of disposal Note for the battery symbol bottom two symbol...

Страница 24: ...a branch of Panasonic Marketing Europe GmbH Maxis 2 Western Road Bracknell Berkshire RG12 1RT Manufactured by Panasonic Corporation 1006 Oaza Kadoma Kadoma City Osaka 571 8501 Japan Importer Panasonic...

Отзывы: