Freeze prevention
During COOL or DRY operation, freezing is detected and
operation is stopped when the temperature of the indoor heat
exchanger matches the conditions below.
1. Freeze-prevention operation is engaged when the
temperature of the indoor heat exchanger is below 43°F(6°C).
2. Restart after freeze-prevention operation occurs when the
temperature of the indoor heat exchanger reaches 46°F(8°C)
or above.
a.
Area: Automatic capacity control
b.
When the temperature drops below Point A, the operation
frequency is reduced by a certain proportion.
c.
Area: Frequency increase is prohibited.
d.
When the temperature reaches Point C or above, freezing
prevention is ended and control is the same as in the
a
area.
*
When the temperature drops to below 36°F(2°C) (continuously
for 2 minutes or longer), the compressor stops.
Once the freeze condition is detected, the air conditioner will
work less than the maximum frequency until it is turned off.
The Freeze Prevention Control during the Low Ambient Cooling
Mode (outside air temperature:59°F(15°C) or lower) is as follows.
The compressor stops when the temperature of indoor heat
exchanger becomes less than 36°F(2°C).
The compressor restarts when the temperature of indoor heat
exchanger becomes 46°F(8°C) or higher.
A
*
B
C
a
b
c
d
Indoor heat e
xchanger
temperature
°
F (
°
C)
36
(2)
43
(6)
46
(8)
7-2. Protective Functions
NOTE
(CLxx models only)
34
Содержание CS-MKS12NKU
Страница 23: ...3 DIMENSIONAL DATA Indoor Unit CS MKS7NKU CS MKS9NKU CS MKS12NKU Unit inch mm 852 0 0010 215 00 0 23 ...
Страница 24: ...Unit inch mm Indoor Unit CS MKS18NKU CS MKS24NKU CS MKS18NKU CS MKS24NKU 852 0 0010 216 00 0 24 ...
Страница 43: ......
Страница 44: ...Operating Instructions CS MKS7NKU CS MKS9NKU CS MKS12NKU APPENDIX A 852 6 4181 214 00 2 A 1 ...
Страница 70: ...Operating Instructions CS MKS18NKU CS MKS24NKU 852 6 4181 215 00 1 APPENDIX B A 2 ...
Страница 117: ......
Страница 118: ...DC1111 0 ...