100
18.2 Heat Mode Performance Data
Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C
Voltage: 230V
18.2.1 CS-HZ9RKE / CU-HZ9RKE CS-HZ9RKE-4 / CU-HZ9RKE-4
CS-AZ9RKE / CU-AZ9RKE
Indoor
(°C)
Outdoor WB (°C)
DB
-20/-21
-15/-16
-10/-11
-7/-8
2/1
7/6
12/11
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
24
2761
1546
3580
1652
3521
1647
4043
1652
4699
1620
3158
609
3585
627
20
2800
1470
3630
1570
3630
1566
4100
1570
4820
1560
3200
570
3726
583
16
2884
1394
3739
1489
3739
1485
4223
1489
4858
1475
3443
571
3979
581
18.2.2 CS-HZ12RKE / CU-HZ12RKE
Indoor
(°C)
Outdoor WB (°C)
DB
-20/-21
-15/-16
-10/-11
-7/-8
2/1
7/6
12/11
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
24
3057
1736
3895
1946
3521
1647
4635
2030
5479
2087
4145
897
4705
924
20
3100
1650
3950
1850
3630
1566
4700
1930
5620
2010
4200
840
4890
858
16
3193
1565
4068
1754
3739
1485
4841
1830
5664
1901
4519
842
5222
856
TC - Total Cooling Capacity (kW)
IP
- Input Power (kW)
Содержание CS-HZ9RKE
Страница 28: ...28 11 1 3 Receiver Printed Circuit Board CN RCV 11 1 4 Fuse Printed Circuit Board ACL501 ACN501 ACL502 ACN502 ...
Страница 95: ...95 17 1 1 4 To remove control board Figure 6 17 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 ...
Страница 96: ...96 Figure 8 Figure 9 ...
Страница 97: ...97 Figure 10 ...