13.8 <Reference> Analysis method for no error code, no cooling / no
warming
13.8.1 Preparation for appropriate diagnosis
In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing
operation (rated operation)] is required.
1. Method of rated operation (rated operation)
For the models which have two buttons of “emergency operation and forced cooling operation”, press forced
cooling button once. For the models which have only emergency operation button, press the button once for 5
seconds and when hear “beep” sound, release the button. Then, cooling operation starts.
2. Checking the mal-functions of indoor / outdoor units
1) Any obstacles against heat release and air suction? (short circuit)
(Forget to remove the outdoor unit cover or fallen leaves blocking the outdoor unit)
2) Are the indoor unit air filters clean? (obstructing heat suction)
3) Is the setting temperature on the remote controller correct? (is the setting temperature set at lower/higher
than the room temperature?)
13.8.2 Understanding and verification of refrigerant cycle
H
eat
exc
han
ge
r
H
eat
exc
han
ge
r
Compressor
(
COMP
)
4-way
valve
Condenser
(
COND
)
Expansion
valve
Liquid side
2-way
valve
Gas side
3-way
valve
High temp
High pressure
Air
Mid temp /
High pressure
Liquid
Low
temp/
Pressure
liquid
Low temp
Low pressure
Air
Evaporator
(
EVA
)
FM
Fan
Fan
Capillary tube
Indoor unit
Temp difference
Suction temp
<
Cooling
>
8
or more
Release temp
<
Heating
>
14
or more
*Measured after 15 mins with strong
fan operation
(Cooling)
Gas pressure
0.9~1.2MPa
Low temp /
Low pressure
Air
Low temp /
Low pressure
liquid
(Cooling
Heating
)
High temp /
High pressure
Air
Mid temp /
high pressure
liquid
Low temp /
Low pressure
Liquid
Low temp /
Low pressure
Air
Mid temp /
High temp
liquid
(Heating)
Gas pressure
2.2~ 3.0MPa
Release temp
Outdoor temp
Suction temp
Heat exchanger
temp
Heat exchanger
temp
High temp / high
pressure
Air
「
Indoor
「
」
Outdoor
」
1. Measuring
temperature
1) Indoor unit suction temperature, release temperature, temperature difference,
→
Measure by thermometer
2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark
:
5 ~ 10°C), in heating mode
is medium temperature (benchmark
:
25 ~ 35°C).
3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark
:
7 ~ 15°C) in heating mode is
high temperature (benchmark
:
38 ~ 50°C).
2. Measuring electric current
Measuring electric current in operation
→
check by clump meter (refer to table of technical characteristic
guideline)
3. Meauring
pressure
Measuring gas pressure
→
check the pressure by manifold gauge (refer to table of technical characteristic
guideline)