99
Remedy
1. Turn off the main power.
↓
2. Connect the disconnected wire correctly.
↓
3. Turn on the main power.
↓
4. After 1 minute, start the operation using the remote control.
(Indoor unit operation will start according to the remote control setting.)
(Outdoor unit operation will start after 3-5 minutes.)
12.4. Test operation and self-diagnosis
12.4.1.
Test Run (Forced Cooling mode)
1. Always use a properly-insulated tool to operate the switch on the circuit board.
(Do not use your finger or any metallic object.)
2. Never turn on the power supply unit until all installation work has been completed.
3. Turn on the circuit breaker before test operation extends past 12 hours.
4. Check that the voltage is -10% of the rated voltage (198V or 342V, 3 phase) or higher when starting the unit.
The unit will not operate if the voltage is less than -10% of the rated voltage (198V or 342V, 3 phase).
5. If test operation continue more than 30 minutes, test operation finishes and shift to normal operation.
6. Test operation mode can be selected cooling mode.
12.4.2.
Test operation from the outdoor unit
During emergency operation or when test operation is carried out, the LED on the P.C.B. will turn on.
Содержание CS-F24DTE5
Страница 18: ...18 4 Dimensions 4 1 CS F24DTE5 CS F28DTE5 ...
Страница 19: ...19 4 2 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 20: ...20 4 3 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Страница 21: ...21 4 4 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 22: ...22 5 Refrigeration Cycle 5 1 CS F24DTE5 CU J24DBE5 CU J24DBE8 CS F28DTE5 CU J28DBE5 CU J28DBE8 ...
Страница 23: ...23 5 2 CS F34DTE5 CU J34DBE5 CU J34DBE8 CS F43DTE5 CU J43DBE8 CS F50DTE5 CU J50DBE8 ...
Страница 24: ...24 6 Block Diagram 6 1 CS F24DTE5 CS F28DTE5 CS F34DTE5 CS F43DTE5 CS F50DTE5 6 2 CU J24DBE5 CU J28DBE5 ...
Страница 25: ...25 6 3 CU J34DBE5 6 4 CU J24DBE8 CU J28DBE8 6 5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 26: ...26 7 Wiring Diagram 7 1 CS F24DTE5 CS F28DTE5 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 27: ...27 7 2 CU J24DBE5 CU J28DBE5 ...
Страница 28: ...28 7 3 CU J34DBE5 ...
Страница 29: ...29 7 4 CU J24DBE8 CU J28DBE8 ...
Страница 30: ...30 7 5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 32: ...32 8 2 Remote Control Display ...
Страница 33: ...33 8 3 Remote Control Panel ...
Страница 115: ...115 13 3 Reaching distance Cooling Mode CS F24DTE5 CS F28DTE5 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 116: ...116 13 4 Sound data ...
Страница 117: ...117 ...
Страница 118: ...118 ...
Страница 119: ...119 ...
Страница 120: ...120 ...
Страница 121: ...121 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Страница 125: ...125 13 7 Discharge and suction pressure SATURATION TEMPERATURE OF DISCHARGE AND SUCTION PRESSURE COOLING ...
Страница 127: ...127 14 Exploded View Indoor Unit 14 1 CS F24DTE5 CS F28DTE5 ...
Страница 128: ...128 14 2 CS F24DTE5 CS F28DTE5 ...
Страница 129: ...129 14 3 CS F24DTE5 CS F28DTE5 ...
Страница 132: ...132 16 Exploded View Indoor Unit 16 1 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 133: ...133 16 2 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 134: ...134 16 3 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Страница 137: ...137 18 Exploded View Outdoor Unit 18 1 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Страница 138: ...138 18 2 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Страница 140: ...140 20 Exploded View Outdoor Unit 20 1 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 141: ...141 20 2 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 142: ...142 20 3 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Страница 144: ...144 22 Print Pattern 22 1 Indoor Unit Printed Main ...
Страница 145: ...145 22 2 Indoor Unit Printed Indicator 22 2 1 Outdoor Unit Main PHAAM Printed in Malaysia SSBZ0603 02 ...