3. Explanation of operation
1) At the deice starting signal, the compressor frequency is set to the value as previously mentioned.
2) At 120 sec. after deice starting signal generated, 4 way valve OFF and at the same time outdoor fan is OFF, indoor fan is OFF,
compressor frequency is set to the previously mentioned value.
3) WIthin 30 sec. after the 4 way valve OFF, the compressor frequency is set to the previously mentioned value.
4) If the outdoor heat exchanger temperature is above a°C, the compressor frequency is set to the value as previously mentioned.
5) After the compressor frequency is changed according to the item 4), in case either outdoor heat exchanger temperature more than b°C
or 10.5 minutes lapsed after 4 way valve OFF is fulfilled, 30 sec. calculation start.
6) After 5) operated, if the outdoor heat exchanger temperature is more than c°C or 30 sec. lapsed, deice operation completion signal
transmit, the compressor frequency is set to the previously mentioned value. And timingly ON signal transmit on outdoor FM.
7) After 59 sec. lapsed after deice operation completion signal generated, 4 way valve/indoor fan is ON, compressor frequency become
FREE, and recover to normal heating operation.
4. Deice operation judgement condition
When any of below a, b, c, d condition is satisfied, deice signal is produced.
a. Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature
< -6°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
b. Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature
< -7°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
c.
Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature
< -9°C for 3 minutes and outdoor air temperature
-3°C and Comp. is ON.
d. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature
< -11°C for 3 minutes and outdoor air temperature < -3°C and Comp. is ON.
However, the first deice will start only after minimum of 60 minutes in operation.
(2nd deice and onward shall follow above conditions)
43
CS-E9DKDW CU-E9DKD / CS-E12DKDW CU-E12DKD
Содержание CS-E9DKDW
Страница 12: ...4 2 Outdoor Unit 4 2 1 CU E9DKD CU E12DKD 12 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 13: ...5 Refrigeration Cycle Diagram 13 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 14: ...6 Block Diagram 14 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 15: ...7 Wiring Diagram 15 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 26: ...2 Heating ii Auto Fan Speed 1 Cooling 26 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 81: ...13 1 2 CS E12DKDW CU E12DKD 81 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 94: ...94 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 95: ...How to use electronic circuit diagram 95 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 96: ...18 3 Remote Control 96 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...
Страница 97: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 97 CS E9DKDW CU E9DKD CS E12DKDW CU E12DKD ...