15.5.19. H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
During heating operation, the temperature detected by the indoor pipe temperature sensor is above 60
e
C.
Malfunction Caused
•
Air short circuit at indoor unit
•
Clogged indoor unit air filter
•
Dust accumulation on the indoor unit heat exchanger
•
2/3 way valve closed
•
Faulty indoor unit fan motor
•
Excessive refrigerant
•
Clogged expansion valve or strainer
•
Faulty indoor pipe temperature sensor
•
Faulty indoor unit PCB
Troubleshooting
Содержание CS-E24LKES
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 11: ...11 5 2 Outdoor Unit ...
Страница 12: ...12 6 Refrigeration Cycle Diagram ...
Страница 13: ...13 7 Block Diagram ...
Страница 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24LKE ...
Страница 16: ...16 8 2 2 CU E28LKE ...
Страница 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24LKE ...
Страница 19: ...19 9 2 2 CU E28LKE ...
Страница 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 24: ...24 10 2 2 Power Printed Circuit Board ...
Страница 90: ...90 16 1 3 To remove power electronic controller ...
Страница 91: ...91 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Страница 92: ...92 16 1 6 To remove cross flow fan and indoor fan motor ...
Страница 93: ...93 ...
Страница 107: ...107 18 2 Outdoor Unit 18 2 1 CU E24LKE ...