55
15.2 Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
Cooling Mode
Heating Mode
Condition of the
air conditioner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Ô
Ô
Ô
Ô
Ô
Ô
Clogged capillary tube
or Strainer
Ô
Ô
Ô
Ò
Ò
Ò
Short circuit in the indoor unit
Ô
Ô
Ô
Ò
Ò
Ò
Heat radiation deficiency
of the outdoor unit
Ò
Ò
Ò
Ô
Ô
Ô
Inefficient compression
Ò
Ô
Ô
Ò
Ô
Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание CS-E12QD3EAW
Страница 22: ...22 5 Dimensions 5 1 Indoor Unit AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 23: ...23 5 2 Outdoor Unit AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 24: ...24 6 Refrigeration Cycle Diagram AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 25: ...25 7 Block Diagram AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 28: ...28 9 Electronic Circuit Diagram 9 1 Indoor Unit AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 29: ...29 9 2 Outdoor Unit AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 39: ...39 11 1 6 1 WIRE STRIPPING AND CONNECTING REQUIREMENT AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 57: ...57 15 4 Error Codes Table AMP Air Conditioning www ampair co uk sales ampair co uk ...