14.2. Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
• Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.3. Breakdown Self Diagnosis Function
Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of
three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below
breakdown diagnosis method:
• Press “CHECK” button at remote controller continuously for more than five seconds to turn on the diagnosis mode, “H11” will be
displayed at remote controller.
• By pressing the TMER “ ” button once, next error code will be displayed; press “V” button once, previous error code will be
displayed.
• If error code displayed matches the error code saved in unit memory (abnormality detected), “beep, beep, beep....” sounds will
be heard for 4 seconds and Power LED will light on. Otherwise, one “beep” sound is heard.
If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off.
Condition of the air conditoner
Cooling Mode
Heating Mode
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the
outdoor unit
Inefficient compression
Содержание CS-E12HKEA
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Страница 11: ...11 5 2 Outdoor Unit ...
Страница 13: ...13 7 Block Diagram ...
Страница 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 15: ...15 8 2 Outdoor Unit ...
Страница 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 17: ...17 9 2 Outdoor Unit ...
Страница 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 19: ...19 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Panel ...
Страница 20: ...20 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 23: ...23 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 39: ...39 ...
Страница 40: ...40 15 2 Indoor Cross Flow Fan and Fan Motor ...
Страница 41: ...41 ...
Страница 43: ...43 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS E9HKEA CU E9HKEA ...
Страница 44: ...44 ...
Страница 45: ...45 ...
Страница 46: ...46 ...
Страница 47: ...47 16 1 2 CS E12HKEA CU E12HKEA ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 50: ...50 ...