– 22 –
MAC9512086C2
CS-C73KE
Operation Details
– Fan Speed control button is pressed.
– Sleep mode button is pressed ON.
– Operation mode is changed.
8) Random Auto Restart Control
• If there is a power failure, operation will be automatically restarted after 3 to 5 1/2 minutes when the power is
resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• This control can be omitted by open the circuit of J X 1. (Refer Circuit Diagram)
9) Indoor Fan Speed Control
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the
table.
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection
button.
Normal
Powerful
Economy
Normal
Powerful
Economy
Normal
Powerful
Economy
Normal
Powerful
Economy
Manual Fan Speed
Auto Fan Speed
Cooling
Mode
Soft Dry Mode
Air Circulation Mode
Hi
t
t
Lo
t
t
t
t
t
Me
t
t
SLo
t
t
t
Random Speed
t
t
SHi
t
t
Can setting by Remote Control
Cannot setting by Remote Control
*
SLo: Indoor Fan rotates at 4-second intervals at Low speed.
*
Lo, Lo¯ or Lo¯¯ Fan Speed is operated randomly during Random Fan Speed.
Random Fan Speed
Random
Fan Speed
Time
Fan Motor
A
10"
ON
4.5" 0.5" 4.5" 0.5"
OFF
OFF
4"
1"
4"
1"
OFF
OFF
ON
ON
ON
ON
B
LO¯
C
LO¯¯
LO
Untitled-1
6/28/00, 4:11 PM
22