– 20 –
MAC9512086C2
CS-C73KE
Operation Details
3) Air Circulation Mode Operation
• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences
at low airflow volume. It stops when the temperature drops to 2
°
C below the setting temperature.
Air Circulation Mode Operation Time Diagram
Operation
Stop
4) Automatic Mode Operation
Standard for Determining Operation Mode
(a) Indoor fan operates at Lo fan speed for 20 seconds.
(b) After judging indoor air temperature, the operation mode is determined and operation continued at the mode
determined.
(c) After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation
includes Cooling mode operation.
(d) Room temperature adjustment.
The following are added to the setting temperature specified as above.
(e) The mode judging temperature and standard setting temperature can be increased by 2
°
C, by open the circuit of
J X 2 at indoor electronic controller.
Cooling Mode
Soft Dry Mode
Setting Temperature (Standard)
25
°
C
22
°
C
Cooling Mode
Soft Dry Mode
↑
Intake Air
Temperature
Cooling
27
°
C
25
°
C
23
°
C
Soft Dry
24
°
C
22
°
C
20
°
C
Higher
→
+2
°
C
Standard
→
±
0
°
C
Lower
→
–2
°
C
Cooling Mode
Soft Dry Mode
Setting Temperature (Standard)
27
°
C
24
°
C
Cooling
Soft Dry
↑
Intake Air
Temperature
ON
Setting
Temp.
OFF
Compressor
Indoor Fan
Outdoor Fan
Operation
Indication LED
2
°
C
Intake Air Temp.
a b c d e
Lo
Lo
23
°
C
25
°
C
Untitled-1