36
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When “OFF/ON” button is pressed.
• During any operation with Patrol, “Patrol” button is pressed again.
• When “e-ion” button is pressed.
• When OFF Timer activates.
c. Patrol operation disable
• To disable the Patrol Operation during unit start (default) with “OFF/ON” button, press “Patrol” button and hold for 5
seconds, then release.
• To disable the Patrol Operation, press “Patrol” button and hold for 15 seconds, then release.
3. Control Content
a. Gas Sensor Control
• First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is
monitored. The Air Dirtiness level is set to level 2.
• After that, gas sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
• The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to
time to get the Air Dirtiness Value.
• There are 3 air dirtiness level, based on the Air Dirtiness Value:
- Air Dirtiness level 0: Clean
- Air Dirtiness level 1: Moderate
- Air Dirtiness level 2: Contaminated
- Dirtiness level sensitivity adjustment.
It is possible to change the gas sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
a. Press and release “SET” button.
b. Press “Timer increment” / “Timer decrement” button to select sensitivity. (Low <
–
> Standard (Default) <
–
> High)
c. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
d. LCD returned to original display if remote control does not operate for 30 seconds.
b. e-ion Control
• When dirtiness level is 1 or 2, e-ion operation starts.
• If dirtiness level improves from level 2 to level 1, the unit carries out level change after 60 seconds.
• When dirtiness level returns to level 0 continuously for 10 minutes or more, e-ion operation stops.
Dirtiness Level Shift
• For Auto Fan Speed, the fan speed increased based on dirtiness level:
Содержание CS-C28GKF
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit ...
Страница 10: ...10 5 2 Outdoor Unit ...
Страница 11: ...11 6 Refrigeration Cycle Diagram ...
Страница 12: ...12 7 Block Diagram ...
Страница 13: ...13 8 Wiring Connection Diagram ...
Страница 14: ...14 9 Electronic Circuit Diagram ...
Страница 15: ...15 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Страница 16: ...16 ...
Страница 17: ...17 10 2 Power Printed Circuit Board ...
Страница 18: ...18 10 3 Indicator panel ...
Страница 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 46: ...46 ...
Страница 47: ...47 ...
Страница 48: ...48 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Страница 49: ...49 ...
Страница 50: ...50 16 Technical Data 16 1 Thermostat Characteristics 1 Characteristics of thermostat ...
Страница 51: ...51 16 2 Operation Characteristics ...
Страница 52: ...52 ...
Страница 54: ...54 ...