12.15 ECO Patrol Operation
•
A Pyoelectric infrared sensor is used to detect injection strength variation of infrared at setting area to determine
the presence or absence of human and its activity level. Human detection area is shown in figure below:
•
ECO Patrol operation – Human presence/absence detection outlined
flow
Process infrared sensor output signal
Human detection (movement) every 3 seconds.
▼
Human detection records
Records human detection (movement) result for 30 seconds and determine its activity level i.e. Hi/Lo.
▼
Presence / absence detection
Compares current and previous human detection result every 30 seconds to determine the presence
or absence of human.
▼
Presence / absence determination
Based on human presence / absence detection, if human presence detection showed within 30
minutes, it is recognised that human is present. If human absence detection showed continuously for
more than 30 minutes, it is recognised that no human is present.
•
ECO Patrol Sensor abnormality detection
(1) Connnector pulled out (disconnected), Wire cut Abnormality (Fix Output at Hi)
c
Abnormal judgment start condition.
Start from ECO Patrol Sensor power ON, and end after 30 seconds.
d
Control content.
Judge ECO Patrol Sensor power level every 100ms.
e
Abnormal Judgment condition.
When ECO Patrol Sensor has continues for 25 seconds Hi level.
(2) Circuit Abnormal (Fix Output Lo)
c
Abnormal judgment start condition.
After ECO Patrol Sensor unit power ON, and after pressed 70 seconds.
d
Control content.
Judge ECO Patrol Sensor power level every 100ms.
e
Abnormal Judgment condition.
When ECO Patrol Sensor has continues at Lo level for 25 seconds.
(3) Abnormal treatment
Any one of the above self-diagnosis result is abnormal
•
Abnormal c1 and ECO Patrol Sensor power supply OFF.
•
After ECO Patrol Sensor unit power is OFF for 5 seconds, Retry the ECO Patrol operation.
•
When Abnormal counter reach 4 counts, ECO Patrol sensor abnormality is confirmed.
(Abnormal counter is cleared when sensor power ON and maintain normal for 120 seconds and above or
Clear Anormal counter by power reset)
•
Save ECO Patrol Sensor Abnormality H59 (no Timer LED blinking).
•
ECO Patrol Sensor operation OFF, but ECO Patrol LED maintain ON.
•
The unit still operate as normal.
•
Sensor error counter can be cleared only after power supply reset or AC Reset button on the remote
control is pressed.
Содержание CS-C12KKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9KKV CS C12KKV ...
Страница 14: ...14 5 1 2 CS C18KKV CS C24KKV CS C28KKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9KKV 5 2 2 CU C12KKV ...
Страница 16: ...16 5 2 3 CU C18KKV CU C24KKV CU C28KKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9KKV CU C9KKV CS C12KKV CU C12KKV ...
Страница 19: ...19 7 1 2 CS C18KKV CU C18KKV CS C24KKV CU C24KKV ...
Страница 20: ...20 7 1 3 CS C28KKV CU C28KKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9KKV CU C9KKV ...
Страница 27: ...27 9 2 CS C12KKV CU C12KKV ...
Страница 28: ...28 9 3 CS C18KKV CU C18KKV ...
Страница 29: ...29 9 4 CS C24KKV CU C24KKV ...
Страница 30: ...30 9 5 CS C28KKV CU C28KKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 32: ...32 10 1 2 Power Printed Circuit Board 10 1 2 1 CS C9KKV CS C12KKV ...
Страница 33: ...33 10 1 2 2 CS C18KKV CS C24KKV CS C28KKV ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 76: ...76 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 78: ...78 Figure 10 Figure 11 ...
Страница 80: ...80 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 82: ...82 Figure 21 Figure 22 Figure 23 ...
Страница 84: ...84 16 3 1 3 To remove power electronic controller Figure 26 Figure 24 Figure 25 Figure 27 ...
Страница 86: ...86 Figure 31 Figure 32 Figure 33 ...