61
12.14
E-ion operation
•
This operation provides clean air by producing negative ions to attract dust captured at the positively charged
active e-ion filters.
•
e-ion operation start condition
o
During unit running at any operation mode, if “e-ion” operation is selected, combination operation (operation
mode + e-ion operation) starts.
o
During unit is OFF, if “e-ion” operation is selected, e-ion individual operation starts.
•
e-ion operation stop condition
o
When “OFF/ON” button is pressed to stop the operation.
o
When “PATROL/e-ion” button is pressed.
o
When OFF Timer activates.
•
e-ion operation pause condition
o
When indoor fan stop (during deice, odor cut control, thermostat off, etc.). e-ion operation resume after
indoor fan restarts.
o
When indoor intake temperature
≥
40°C. e-ion operation resume after indoor intake temperature < 40°C
continuously for 30 minutes.
•
Indoor
fan
control
o
During any operation mode combines with e-ion operation, fan speed follows respective operation mode.
o
During e-ion individual operation – only Auto Fan Speed and no Powerful operation is allowed. Even if Fan
Speed button is pressed, no signal is sent to air conditioner, and no change on LCD display.
Auto Fan Speed for e-ion operation switches from SHi to Hi after 4 hours of operation.
•
Airflow direction control
o
During any operation mode combines with e-ion operation, airflow direction follows respective operation
mode.
o
During e-ion individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no
signal is sent to air conditioner, and no change on LCD display.
•
Timer
control
o
When ON timer activates when unit stops, previous operation resumes and restored last saved e-ion
operation status.
o
When ON timer activates during any operation, no change and carry on current operation.
o
When OFF timer activates during any operation, all operation stops and the latest e-ion operation status is
saved.
•
Indicator
o
When e-ion operation starts, e-ion indicator ON.
•
Remote Control Receiving Sound
o
Normal
Operation
Î
e-ion Operation
: Beep
o
e-ion
Operation
Î
Normal Operation
: Beep
o
Stop
Î
e-ion individual Operation
: Beep
o
e-ion individual Operation
Î
Stop
:
Long
Beep
•
Power
failure
o
During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation
resumes immediately.
o
During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
o
e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air
conditioner operates without e-ion operation.
Содержание CS-C12KKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9KKV CS C12KKV ...
Страница 14: ...14 5 1 2 CS C18KKV CS C24KKV CS C28KKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9KKV 5 2 2 CU C12KKV ...
Страница 16: ...16 5 2 3 CU C18KKV CU C24KKV CU C28KKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9KKV CU C9KKV CS C12KKV CU C12KKV ...
Страница 19: ...19 7 1 2 CS C18KKV CU C18KKV CS C24KKV CU C24KKV ...
Страница 20: ...20 7 1 3 CS C28KKV CU C28KKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9KKV CU C9KKV ...
Страница 27: ...27 9 2 CS C12KKV CU C12KKV ...
Страница 28: ...28 9 3 CS C18KKV CU C18KKV ...
Страница 29: ...29 9 4 CS C24KKV CU C24KKV ...
Страница 30: ...30 9 5 CS C28KKV CU C28KKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 32: ...32 10 1 2 Power Printed Circuit Board 10 1 2 1 CS C9KKV CS C12KKV ...
Страница 33: ...33 10 1 2 2 CS C18KKV CS C24KKV CS C28KKV ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 76: ...76 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 78: ...78 Figure 10 Figure 11 ...
Страница 80: ...80 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 82: ...82 Figure 21 Figure 22 Figure 23 ...
Страница 84: ...84 16 3 1 3 To remove power electronic controller Figure 26 Figure 24 Figure 25 Figure 27 ...
Страница 86: ...86 Figure 31 Figure 32 Figure 33 ...