73
RPM shift
+0
+20
+40
+70
(ID temp) Pipe
6.0°C
4.0°C
2.0°C
5.0°C
7.0°C
3.0°C
Compressor starts for
≥
5 minutes
▲
T
≤
2.5°C for 2 minutes
Compressor
OFF
Compressor
restart
▲
T = Intake air temperature – Indoor heat exchanger temperature
14.5 Freeze Prevention Control
•
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to
compressor.
•
This control will activate when temperature of indoor heat exchanger falls below 2°C continuously for more than 4
minutes and compressor turn off.
10
Recovery
4 min
2
Indoor Heat
Exchanger
Temperature
(°C)
Compressor
OFF
•
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed
will be increased according to the indoor pipe temperature as below figure: (Applicable for C9KKH and C12KKH
ONLY)
•
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
•
Restart control (Time Delay Safety Control) will be applied in this control if the recovery time is too short.
14.6 Compressor Reverse Rotation Protection Control
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuously 2 minutes, compressor will stop and restart
automatically.
•
Time Delay Safety Control is activated before the compressor restart.
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
•
If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
•
The 5 Times counter can be reset when either one of the following condition happen:
o
Unit is OFF by remote control or AUTO OFF/ON button.
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Operation mode change.
•
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
•
TIMER LED blinking will be reset if:
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Power supply reset.
Содержание CS-C12KKF-2
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 11: ...11 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C12KKF 2 ...
Страница 12: ...12 5 1 2 CS C18KKF 2 CS C24KKF 2 CS C28KKF 2 ...
Страница 13: ...13 5 2 Outdoor Unit 5 2 1 CU C12KKF 2 CU C18KKF 2 ...
Страница 14: ...14 5 2 2 CU C24KKF 2 CU C28KKF 2 ...
Страница 16: ...16 7 Block Diagram 7 1 1 CS C12KKF 2 CU C12KKF 2 ...
Страница 17: ...17 7 1 2 CS C18KKF 2 CU C18KKF 2 CS C24KKF 2 CU C24KKF 2 ...
Страница 18: ...18 7 1 3 CS C28KKF 2 CU C28KKF 2 ...
Страница 23: ...23 9 Electronic Circuit Diagram 9 1 CS C12KKF 2 CU C12KKF 2 ...
Страница 24: ...24 9 2 CS C18KKF 2 CU C18KKF 2 ...
Страница 25: ...25 9 3 CS C24KKF 2 CU C24KKF 2 ...
Страница 26: ...26 9 4 CS C28KKF 2 CU C28KKF 2 ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Power Printed Circuit Board 10 1 2 1 CS C12KKF 2 ...
Страница 29: ...29 10 1 2 2 CS C18KKF 2 CS C24KKF 2 CS C28KKF 2 ...
Страница 50: ...50 13 1 2 Cooling Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 52: ...52 13 2 2 Soft Dry Operation Time Diagram For CS C18KK CU C18KK CS C24KK CU C24KK and CS C28KK CU C28KK ...
Страница 80: ...80 Figure 3 Figure 4 Figure 5 17 1 1 3 To remove discharge grille Figure 6 ...
Страница 82: ...82 Figure 10 Figure 11 ...
Страница 84: ...84 17 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 86: ...86 Figure 21 Figure 22 Figure 23 ...
Страница 88: ...88 17 3 1 3 To remove power electronic controller Figure 26 Figure 24 Figure 25 Figure 27 ...
Страница 90: ...90 Figure 31 Figure 32 Figure 33 ...
Страница 100: ...100 19 2 CS C18KKF 2 CU C18KKF 2 Cooling Capacity Performance Data 220V Cooling Capacity Performance Data 240V ...
Страница 101: ...101 19 3 CS C24KKF 2 CU C24KKF 2 Cooling Capacity Performance Data 220V Cooling Capacity Performance Data 240V ...
Страница 102: ...102 19 4 CS C28KKF 2 CU C28KKF 2 Cooling Capacity Performance Data 220V Cooling Capacity Performance Data 240V ...