47
13 Protection Control
13.1. Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature and compressor OFF temperature during the period.
• This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
•
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
•
The reason of the difference is to reduce the starting current flow.
13.5. Freeze Preventive Control
• To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
• This control will activate when the temperature of indoor heat exchanger falls below 2
°
C continuously for more than 4 minutes.
• The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature
reaches certain temperature for 5 sec. the speed will be increased as in below figure.
• Compressor will turn off when indoor temperature falls below 2
°
C for more than 4 minutes. It will restart again when indoor heat
exchanger temperature rises to 10
°
C.
• Restart control (Time Delay Safety Control) will be applied in this control.
Содержание CS-A12HKD
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Outdoor Unit ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS A7HKD CS A9HKD CS A12HKD ...
Страница 14: ...14 5 2 Outdoor Unit 5 2 1 CU A7HKD CU A9HKD 5 2 2 CU A12HKD ...
Страница 15: ...15 6 Refrigeration Cycle Diagram ...
Страница 16: ...16 7 Block Diagram 7 1 CS A7HKD CU A7HKD CS A9HKD CU A9HKD ...
Страница 17: ...17 7 2 CS A12HKD CU A12HKD ...
Страница 20: ...20 9 Electronic Circuit Diagram ...
Страница 21: ...21 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Страница 22: ...22 10 2 Power Printed Circuit Board TOP VIEW BOTTOM VIEW ...
Страница 23: ...23 10 3 Indicator Printed Circuit Board 10 4 Patrol Printed Circuit Board ...
Страница 26: ...26 3 For the embedded piping This can be used for left rear piping and left bottom piping also ...
Страница 51: ...51 Normal Deice Time Diagram Overload Deice Time Diagram ...
Страница 57: ...57 ...
Страница 58: ...58 16 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Страница 59: ...59 ...
Страница 60: ...60 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry Heating ...
Страница 61: ...61 17 2 Operation Characteristics 17 2 1 CS A7HKD CU A7HKD ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 ...
Страница 65: ...65 17 2 2 CS A9HKD CU A9HKD ...
Страница 66: ...66 ...
Страница 67: ...67 ...
Страница 68: ...68 ...
Страница 69: ...69 17 2 3 CS A12HKD CU A12HKD ...
Страница 70: ...70 ...
Страница 71: ...71 ...
Страница 72: ...72 ...