(There is no detection during Outdoor Fan stops.)
- Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to
overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
- Deicing ends when
1. 12 minutes after deicing operation starts;
2. TRS senses the outdoor piping temperature rises to 4°C (TRS
OPEN).
3. Deicing will not end immediately as time delay (Td) is valid as
shown below.
Time taken from deicing starts to TRS OPEN (T)
Td (seconds)
T < 3 minutes
0
3 minutes T < 6 minutes
60
6 minutes T < 9 minutes
120
T 9 minutes
180
- Once deicing operation starts, it will not end for 60 seconds.
- After deicing operation, compressor stops for 30 seconds and 4-
way valve stays at cooling position for 10 seconds.
Normal Deicing Time Diagram
31
Содержание CS-A123KR
Страница 13: ...13 ...
Страница 14: ...5 Refrigeration Cycle Diagram 14 ...
Страница 15: ...6 Block Diagram 15 ...
Страница 16: ...7 Wiring Diagram 16 ...
Страница 17: ...REMARKS B BLUE BR BROWN BL BLACK W WHITE R RED O ORANGE P PINK Y G YELLOW GREEN 17 ...
Страница 29: ...29 ...
Страница 32: ...Overload Deicing Time Diagram 32 ...
Страница 49: ...3 For the embedded piping 49 ...
Страница 50: ... This can be used for left rear piping and left bottom piping also 50 ...
Страница 75: ...75 ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...15 Exploded View 80 ...
Страница 89: ...How to use electronic circuit diagram 89 ...
Страница 90: ...TIMER TABLE 90 ...
Страница 92: ...22 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 92 ...
Страница 93: ...22 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 93 ...
Страница 94: ... MACC Printed in Malaysia 94 ...