FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND 
CHECK AFTER INSTALLATION IS FINISHED.

Items to be checked after completion of work

2-4 NOTE TO THE INSTALLER

Read this manual carefully to ensure correct installation. Be sure to instruct the customer how to operate 
the system showing him/her the enclosed operation manual.

Explain to the customer what system is installed on the site and be sure to fill in what is required in the col-
umn shown on “WHAT TO DO BEFORE OPERATION” of the operation manual.

3. SELECTING INSTALLATION SITE

(1) Select an installation site where the following conditions are satisfied and that meets with your 

customer’s approval.

Where the floor is strong enough to dear the indoor unit weight.

Where the floor is not significantly inclined.

Where nothing blocks the air passage.

Where condensate can be properly drained.

Where sufficient clearance for installation and maintenance can be ensured.

Where there is no possibility of flammable gas leakage.

Where optimum air distribution can be ensured.

Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the instal-
lation manual of the outdoor unit.)

Keep the indoor and outdoor units, power cable and transmission wiring, at least 1 m from TVs and 
radios, to prevent distorted pictures and static. (Depending on the type and source of the electrical 
waves, static may be heard even when more than 1 m away.)

Items to be checked

If not properly done, what is likely to occur

Check

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown 
on the name plate?

The unit may malfunction or the components burn out.

Are wiring and piping correct?

The unit may malfunction or the components burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is wiring size according to specifications?

The unit may malfunction or the components burn out.

Is something blocking the air outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant 
charge noted down?

The refrigerant charge in the system is not clear.

Содержание CS-20PM1HPK

Страница 1: ...NSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄÉÁÂÁÓÔÅ ÐÑÏÓÅÊÔÉÊÁ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓ ÐÑÉÍ ...

Страница 2: ... result in water leakage electric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water leakage electric shocks fire or the unit falling Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling a...

Страница 3: ...ng copper pipes or soldered parts may result in refrigerant leakage c near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment d where flammable gases may leak where there are carbon fiber or ignitable dust suspensions in the air or where volatile flammables such as thinner or gasoline are handl...

Страница 4: ... object in fan heater stove cooking appliance etc may result in production of toxic gases This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environ ment If installed as a household appliance it could cause electromagnetic interference 2 2 ACCESSORIES Check the following accessories are included with your unit 2 3 OPTIONAL ACCESSORIES These are two ...

Страница 5: ...or units is possible within the allowable limit Refer to the instal lation manual of the outdoor unit Keep the indoor and outdoor units power cable and transmission wiring at least 1 m from TVs and radios to prevent distorted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1 m away Items to be checked If not properly done what is...

Страница 6: ...ite order Pull towards the front unit the knob snaps in place Maintenance area 80 or more A or more B or more 625 CS 20 25RM1HPK CS 32 40RM1HPK CS 50 63RM1HPK CS 20 25PM1HPK CS 32 40PM1HPK CS 50 63PM1HPK A mm 570 710 990 B mm 1030 1170 1450 IMPORTANT Leave sufficient clearance for air inlet and maintenance Model CS RM1HPK Base CS PM1HPK Window 100 or more PM1HPK 150 or more RM1HPK 100 or more PM1H...

Страница 7: ...y Open the left side lid of control panel and mount the lower case on the remote controller switch 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Be sure to thermally insulate both the gas pipes and fluid pipes Water leakage may result if the pipes are not insulated Only use insulation resistant to at least 120 C Furthermo...

Страница 8: ...will suddenly increase From that posi tion tighten the nut to the angle shown on Tabel 2 Make absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting 3 and 4 Fasten both ends with the clamps 6 attached Refer to Fig 1 Wrap the sealing pad 5 atta...

Страница 9: ... the right drawing 2 After piping work is finished check drainage flows smoothly 3 Be sure to insulate all indoor pipes CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sew age might enter the indoor unit through the drain pipes and corrode the heat exchanger Pipe gauge Tightening torque Flare dimension A mm Flare sh...

Страница 10: ...to the entire system must be installed 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 8 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE NOTES 1 Allowable length of transmission wiring between indoor outdoor units and between the indoor unit and the remote controller is as follows 1 Outdoor unit Indoor unit Max 1000 m T...

Страница 11: ...unit wire as shown in the figure on the right If wiring from the piping side wire as shown in the figure on the right CAUTION When cramping wiring use the included cramping material to do an appropriate cramp to prevent undue pressure on the wiring connections When carrying out the wiring bundle the wires to prevent the switch box lid from lifting and attach the lid firmly When attaching the switc...

Страница 12: ...deteriorate protection 4 Keep transmission wiring at least 50 mm away from power supply wiring The equipment may malfunction if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER 6 Never connect power supply wiring to the terminal board for transmission wiring A mistake of the sort could damage the entire system 7 Use only sp...

Страница 13: ... 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz IN D OUT D F1 F2 F1 F2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 L N Control box Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit For use with 2 remote controllers Power supply 220 240V 50Hz or 220V 60Hz Note It is not necessa...

Страница 14: ...e the switch of the other remote controller set to M 9 4 COMPUTERISED CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal board remote controller to trans mission wiring 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to input A Wire specification Sheathed...

Страница 15: ...TION FORCED OFF at factory set 9 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional controllers for centralized control 10 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an error occurs Check the error code on the liq uid crystal dis...

Страница 16: ... 0110 HT 3VA11734 2A EM01A161 ...

Отзывы: