13
English
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the same system. However, branch switches and
branch circuit breakers must be selected carefully.
2. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
9-3
CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote controllers)
•
When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”.
MAIN/SUB CHANGEOVER
(1) Insert a wedge-head screwdriver into the recess
between the upper and lower parts of remote controller
and, working from the 2 positions, remove carefully the
upper part.
The remote controller PC board is attached to the
upper part of remote controller.
(2) Turn the MAIN/SUB changeover switch on one
of the two remote controllers PC board to “S”.
(Leave the switch of the other remote controller
set to “M”.)
9-4 COMPUTERISED CONTROL (FORCED OFF AND ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
•
Connect the input from outside to terminals T1 and T2 of the terminal board (remote controller to trans-
mission wiring).
(2) Actuation
•
The following table explains FORCED OFF and ON/OFF OPERATIONS in response to input A.
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
0.75 - 1.25 mm
2
Length
Max. 100 m
External terminal
Contact that can ensure the minimum
applicable load of 15 V DC, 10 mA.
FORCED OFF
ON/OFF operation
Input “ON” stops operation (impossible by remote controllers).
Input OFF
→
ON turns ON unit.
Input OFF enables control by remote controller.
Input ON
→
OFF turns OFF unit.
Upper part of
remote controller
Lower part of
remote controller
Insert the screwdriver here and gently work
off the upper part of remote controller.
S
M
S
S
M
Only one remote controller
needs to be changed if
factory settings have
remained untouched.
Remote controller
PC board
(Factory setting)
F2
T1
T2
FORCED
OFF
Input A
Содержание CS-20PM1HPK
Страница 16: ... 0110 HT 3VA11734 2A EM01A161 ...