73
11.2 Outdoor Unit
Attached accessories
Optional Accessory
11.2.1 Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -20°C for UD models and -28°C for
UX models.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinery oil, etc), it
lifespan maybe shorten.
When installing the product in a place where it will
be affected by typhoon or strong wind such as
wind blowing between buildings, including the
rooftop of a building and a place where there is no
building in surroundings, fix the product with an
overturn prevention wire, etc. (Overturn prevention
fitting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Model
Piping size
Rated Length (m)
Max. Elevation (m)
Min. Piping
Length (m)
Max. Piping
Length (m)
Additional
Refrigerant
(g/m)
Gas
Liquid
For Heat Pump
Indoor Unit
For
Hydro
Tank
UX09*E5*, UX12*E5*,
UD12*E5*, UD16*E5*,
UX09*E8*, UX12*E8*,
UX16*E8*, UD09*E8*,
UD12*E8*, UD16*E8*
ø15.88mm
(5/8")
Ø9.52mm
(3/8")
7
5
20
3
30
50
Example:
If piping length is 30m, the quantity of additional refrigerant should be 1000g. [(30-10)m x 50 g/m = 1000g]
GWP (R410A) = 2088
11.2.2 Install the Outdoor Unit
Installation
Diagram
11.2.2.1
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation,
please consult authorized dealer/specialist.
This illustration is for explanation purposes only.
No.
Accessories part
Qty.
No.
Accessories part
Qty.
1
Drain elbow
1
3
Protective bushing
2
2
Rubber cap
8
No.
Accessories part
Qty.
4
Base Pan Heater
CZ-NE3P
1
•
It is strongly recommended to install a Base Pan Heater
(optional) if the outdoor unit is install in cold climate area.
Refer the Base Pan Heater (optional) installation instruction
for details of installation.
Vinyl tape (Wide)
Saddle
Indoor/Outdoor connecting cable
-
For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE
min 4.0mm
2
or 6.0mm
2
-
For UX09*E8*, UX12*E8*, UX16*E8*, UD09*E8*, UD12*E8*,
UD16*E8* use 6-CORE WIRE min 1.5mm
2
Type designation 60245 IEC 57 or heavier cord
ø15.88mm (5/8") Gas refrigerant piping
ø9.52mm (3/8") Liquid refrigerant piping
100m
m
or more
100
0m
m
or
mo
re
100
mm
or
mor
e
300mm
or more
[
]
Check that the cables do not
touch the compressor, etc.