Display of values
KW2M-A/X User's Manual
67
7.2.8 Current
・
The present current value is displayed. (N-phase current is displayed for 3P4W.)
M
- 1
1
A
I
2
k A
3
k A
A
A
1 - 2
1
A
I
2
A
3
A
N
A
・
It measures from 0.1% of CT secondary current.
・
When input current exceeds 200% or the display range, it displays
“
- - - - -
“
.
Check the measurement environment.
・
Current measuring points: The device measures the current as shown below.
Display
1P2W
1P3W
3P3W
3P4W
1
1
st
circuit R-current
R-current
R-current
2
2
nd
circuit R-current
N-current
S-current
3
3
rd
circuit R-current
T-current
T-current
A
Average
Average of R and T
Average
N
-
-
N-current *only 3P4W
7.2.9 Voltage
・
The present voltage is displayed.
・
Press <SHIFT/
∧
> to switch between phase voltage and line voltage.
(Line voltage is not displayed for 1P2W system. Phase voltage is not displayed for 3P3W system.)
Phase voltage
Line voltage
M
- 1
1
V
U
2
V
3
V
A
V
M
- 1
1 2
V
U
2 3
V
3 1
V
A
V
・
When input voltage is under 3V (when VT ratio is 1.), the device displays
“
0.00
”
and does not measure.
・
When input voltage exceeds 828V or the display range, the device displays
“
- - - - -
“
.
Check the measurement environment.
・
Voltage measuring points: The device measures the voltage as shown below.
Display
1P2W
1P3W
3P3W
3P4W
1
R-voltage (L1-N)
or 1
st
circuit R-voltage
R-voltage (L1-N)
No display
R-voltage (L1-N)
2
None or
2
nd
circuit R-voltage
None
S-voltage (L2-N)
3
None or
3
rd
circuit R-voltage
T-voltage (L3-N)
T-voltage (L3-N)
A
Average
Average of R and T
Average
1 2
No display
R-voltage (L1-N)
RS-voltage (L1-L2)
RS-voltage (L1-L2)
2 3
T-voltage (L3-N)
ST-voltage (L2-L3)
ST-voltage (L2-L3)
3 1
TR-voltage (L3-L1)
TR-voltage (L3-L1)
TR-voltage (L3-L1)
A
Average of R and T
Average
Average
SHIF
T
>
SHIF
T
>