Settings
KW2M-A/X User's Manual
47
Item
Description
10
Power factor
Select phase to monitor and set threshold to use for output.
*Select
‘
All
’
when measuring 3P3W.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 9999999999.99
(initial: 9999999999.99)
ON threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)
11
Count value
Set a count value to use for alarm output.
<Range>
0 to 999999 (initial: 0)
12
Over Voltage
Select phase to monitor.
*The threshold is the ratio that is set at
‘
Setting for Power
Measurement
’
.
< List >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
13
Under Voltage
14
Over frequency
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 100.00Hz (initial: 100.00)
ON threshold: 0.00 to 100.00Hz (initial: 100.00)
15
Under frequency
16
Current THD
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 400.00% (initial: 400.00)
ON threshold: 0.00 to 400.00% (initial: 400.00)
17
Voltage THD
18
Current harmonics
19
Voltage harmonics
20
Current unbalancing
Select phase to monitor and set threshold to use for output.
< Range >
OFF threshold: 0.00 to 300.00% (initial: 300.00)
ON threshold: 0.00 to 300.00% (initial: 300.00)
21
Voltage unbalancing
22
Power demand
Select demand type to monitor and set threshold to use for
output.
< List & Range >
Power Type: Active, Reactive, Apparent,
Active(Export), Reactive(Export) (initial: Active)
OFF threshold: 0.000 to 999999999.999 (initial:
999999999.999)
ON threshold: 0.000 to 999999999.999 (initial: 999999999.999)
23
Current demand
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 120.00% (initial: 0.00)