Chapter 1. Programming Site Data
34
DigitalFlow™ XMT868i Programming Manual
Option Card Totalizer Outputs
This type of output issues one pulse per selected volume of flow. The meter produces a pulse each time the
programmed amount of flow passes through the pipe. Complete the following steps to set up the totalizer outputs of
an option card installed in
Slot 1
:
1.
Scroll to the desired
Output
(
A, B, C
or
D
), and press
[Enter]
.
Note:
The set up of output A is used as an example. Identical procedures would be used to set up the other
outputs.
2.
Scroll to
Off
to disable
Output A
and return to step 1, or on
TTLZR
to set up
Output A
as a totalizer output. Press
[Enter]
.
For a 1-Channel meter, skip to step 4.
3.
Scroll to the desired
Channel
option, and press
[Enter]
. See Table 20 on page 33 for a description of the channel
options available at the above prompt.
4.
Scroll to the desired
Measurement Name
, and press
[Enter]
. (Table 19 on page 29 provides a description of the
available parameters.)
Note:
The measurement units that appear in these prompts are those selected in the
GLOBL-SYSTM
menu earlier
in this section.
5.
Enter a value between 50
sec and 500,000
sec for
Min. Pulse On Time
(the frequency of the totalizer pulses)
and press
[Enter]
.
Note:
A complete pulse consists of equal amounts of
ON
and
OFF
times. Choose a value that is compatible with
the counter to be used.
6.
Enter a value for the number of measurement units represented by each pulse, and press
[Enter]
.
After responding to the above prompt, the meter returns to step 1. Press
[Escape]
to proceed to another menu or
option.
Содержание DigitalFlow XMT868i
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 50: ...Chapter 1 Programming Site Data 42 DigitalFlow XMT868i Programming Manual...
Страница 70: ...Chapter 3 Logging Data 10 DigitalFlow XMT868i Programming Manual Figure 21 Typical Log Contents...
Страница 74: ...Chapter 4 Printing Data 2 DigitalFlow XMT868i Programming Manual...
Страница 78: ...Chapter 5 Clearing Data 4 DigitalFlow XMT868i Programming Manual...
Страница 79: ...DigitalFlow XMT868i Programming Manual 5 Appendix A Menu Maps Appendix A Menu Maps...
Страница 80: ...Appendix A Menu Maps 6 DigitalFlow XMT868i Programming Manual...
Страница 86: ...Appendix A Menu Maps DigitalFlow XMT868i Programming Manual...
Страница 144: ...Appendix D PanaView Menu Maps for the XMT868i 70 DigitalFlow XMT868i Programming Manual...
Страница 150: ...Appendix A PanaView Menu Maps DigitalFlow XMT868i Programming Manual 76...
Страница 162: ...Warranty 6 AquaTrans AT868 User s Manual no content intended for this page...
Страница 163: ......