Chapter 3. Wiring Instructions
16
DewPro
®
MMY30 User’s Manual
3.5 Electrical Connections
below shows the electrical connections for the DewPro MMY30.
Figure 10: Electrical Connections
3.6 General Installation Instructions
Complete the following steps to make the DewPro MMY30 wiring connections:
1.
Unscrew the cap on the terminal side of the unit.
2.
Loosen the cable gland located on the side of the unit.
3.
Using a signal cable with standard conductor size, feed the signal cable through the conduit opening.
4.
To relieve any stress on the cable, retighten the metal cable gland to meet IP 67 requirements.
5.
Verify that a voltage between 12 and 28 VDC is present across the terminals and -.
Note:
Because of voltage loss in the wire length, the displays, the indicators, etc., this is the voltage that appears
across the DewPro MMY30 terminals and does not necessarily equal the power supply voltage.
6.
To meet EMI/RFI immunity requirements, a two-wire shielded cable with a common foil shield layer must be used
to power the MMY30. Remove 3” of the cable insulation and pull back the foil so that it is clamped in the metal
cable gland. The ground wire must be connected to the internal DewPro MMY30 grounding screw.
GND
LOOP 1–+
+
–
24 VDC Nominal (12-28V)
External GND/SHIELD Connection
Internal GND Connection
Содержание DewPro MMY30
Страница 1: ...A40251540 Rev D April 2022 Panametrics com DewPro MMY30 User s Manual...
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 8: ...Contents vi DewPro MMY30 User s Manual no content intended for this page...
Страница 34: ...Chapter 5 Troubleshooting 26 DewPro MMY30 User s Manual no content intended for this page...
Страница 38: ...Chapter 6 Technical Specifications 30 DewPro MMY30 User s Manual no content intended for this page...
Страница 42: ...Warranty 34 DewPro MMY30 User s Manual no content intended for this page...