Installing the water heater:

Vertical Vent Installation

A fire stop plate should be installed at every
penetration of a floor or ceiling if the vent is
not running in a fire-rated shaft. Maintain the
recommended air space clearance to
combustible materials and building insulation.

Once the vent terminal location has been
determined, make a hole through the roof and
interior ceiling to accommodate the vent pipe.
Complete the vent pipe installation to the
water heater’s vent connector fitting on the

water heater vent collar outlet. Support
vertical or horizontal runs as previously
mentioned. If required, use silicone sealant 
at the point the vent connector joins the 
water heater.

Install adequate flashing where the vent pipe
passes through the roof. Determine the vent
terminal height and install the vent pipe
accordingly. Refer to the diagram above for
proper vent terminal height.

The vent roof system must terminate at least
1 foot (30 cm) above the roof line and at least
2 feet (61 cm) higher than any portion of the
building within 10 feet (3 m).

Install supports every 5 feet (1.5 m) vertically
along the vent pipe route. Vertical supports
are required after every transition to vertical
and are required after every offset elbow.
When the vent is free-standing and penetrates
a roof/ceiling, another means of support must
be used at a second location.

Follow the vent manufacturer’s recommended
installation instructions provided with the
vent purchased from the manufacturer. 

Chase Requires

6" (15 cm) Clearance

to Combustibles

Firestop

Firestop

Roof Jack

Adjustable
Roof 
Flashing

Vent
Adapter

3" (8 cm) Clearance

Support
Hanger

Condensate

Trap

To Drain. Dispose of

condensate in accordance

to local codes

Storm

Collar

Support

Clamp

1/4" per foot upward slope

2'

(61 cm)

Max

Vertical 
Termination
Adapter

Air Intake

3“/ 5” Concentric Pipe

Standard Vertical Vent Termination

Vertical Vent Termination Location

The location of the vent terminal depends on the following
minimum clearances and considerations (see diagram at left):

Minimum twelve (12) inches (30 cm) above roof.

Minimum twelve (12) inches (30 cm) above anticipated
snow level.

Maximum twenty-four (24) inches (60 cm) above roof level
without additional support for vent.

Four (4) feet (1.2 m) from any gable, dormer or other 
roof structure with building interior access (i.e., vent,
window, etc.).

Ten (10) feet (3 m) from any forced air inlet to the building.
Any fresh or make-up air inlet such as a dryer or furnace
area is considered to be a forced air inlet.

Notice: Only Rheem
approved termination 
and parts should be used
during installation.

Notice: Follow vent
manufacturer’s installation
instructions and their
recommended clearances to
combustibles as required.

14

Min. 12" 

(30 cm) 

Above Roof

Min. 12" 

(30 cm) 

Above Anticipated

Snow Level.

Max. 24" 

(60 cm) 

Above Roof (Without Additional Support)

Vent Pipe
Through Roof

Only Rheem approved
termination and parts
should be used during
installation.

Содержание PTG-53

Страница 1: ...the proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This...

Страница 2: ...ce READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date...

Страница 3: ...er flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible mater...

Страница 4: ...emote control and a dip switch adjustment Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is suppl...

Страница 5: ...e or LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to...

Страница 6: ...ON READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage per...

Страница 7: ...of any flammable liquids which may be improperly stored or accidentally spilled The water heater should be installed as close as practical to the vent termination to minimize vent length and the numbe...

Страница 8: ...entional frame masonry or metal construction infiltration air is normally adequate for proper combustion and ventilation If the water heater is installed in a confined space provisions for combustion...

Страница 9: ...l the appliance vent adapter and properly vent the water heater to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing death seri...

Страница 10: ...and dispose of condensate from venting systems When a water heater is vented horizontally the vent pipe can have a DOWNWARD or UPWARD slope towards the termination If an UPWARD slope is used a condens...

Страница 11: ...let to any building or other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30kW 36 inches 91 cm for appliances 100 000 Btuh 3...

Страница 12: ...maintenance Do NOT extend exposed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Indoor Water Heater 12 WARNING Moisture in the flue...

Страница 13: ...ent seal is made Now attach the female end of the air intake tee to the male end of the 3 5 concentric vent pipe Push firmly on the air intake tee until the outer jacket has made contact with the snap...

Страница 14: ...llow the vent manufacturer s recommended installation instructions provided with the vent purchased from the manufacturer Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Roof Jack A...

Страница 15: ...or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed Operation of the water heater requires the minimum water pressure of...

Страница 16: ...e copper connections are recommended on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check Valve between the water heater and the wa...

Страница 17: ...be installed in the discharge line Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer...

Страница 18: ...the action of LP gas Use compound sparingly on male threads only A sediment trap should be installed at the bottom of the gas line Do not use excessive force over 31 5 ft lbs 42 7 Nm in tightening the...

Страница 19: ...controls can connect to the water heater Therefore a maximum of three controls can connect to the water heater No other manufacturer s controls are suitable for use with this water heater DO NOT atte...

Страница 20: ...the water heater Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in the remote control Fix the control to the base plate at the bottom of th...

Страница 21: ...eration Verify correct operation after servicing BK 8 R GR Y B O W BR WATER FLOW SENSOR OVER HEAT LIMITER BK GND GND THE CONNECTORS OF DUAL AND MULTIPLE LED CONTROL BATH BATH CONTROL1 CONTROL2 ARE INT...

Страница 22: ...Water Filter Drain Valve Drain Hose To Suitable Drain 1 4 Per Foot Downward Pitch NOTICE The National Fuel Gas Code NFGC and B149 mandates a manual gas shut off valve See NFGC B149 for complete instru...

Страница 23: ...y heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or defect caused...

Страница 24: ...sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for...

Страница 25: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Страница 26: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Страница 27: ...otter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burne...

Страница 28: ...nance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply...

Страница 29: ...tructions DO NOT operate the unit if vent system shows signs of leaking exhaust Check to make sure that the air intake and vent outlet on the termination has not been blocked or contain debris Burner...

Страница 30: ...freezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from in...

Страница 31: ...functions if applicable Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water demand Incre...

Страница 32: ...r safety devices Refer repairs to qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconn...

Страница 33: ...as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring gas piping burners vent connectors or other safety devices Refer repairs to qualified ser...

Страница 34: ...then continue as listed below Press the SW2 button on the left hand side of the PCB for more than 1 second The LED on the PCB starts illuminating continuously At the same time the display of the Main...

Страница 35: ...35 Notes...

Страница 36: ...ll be located in the room that houses the appliance or equipment and shall a Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the...

Отзывы: