Installing the water heater:

For increased energy efficiency, use pipe
insulation. Please install the insulation
according to the diagram above, making sure

to insulate all the way to the top. 

Do not

cover any drain or pressure relief valve(s).

Do’s

q

Do

follow all installation instructions

covered in this manual.

q

Do

check inlet gas pressure to ensure 

that it is within the range specified on 
the rating plate.

q

Do 

provide adequate air for combustion

and ventilation as discussed in the
Instruction Manual and the National Fuel
Gas Code (CAN/CGA B149 in Canada).

q

Do 

maintain proper clearances to

combustibles and non-combustibles as
specified on the nameplate.

q

Do 

ensure that the venting system complies

with the guidelines found in the Instruction
Manual and National Fuel Gas Code
(CAN/CGA B149 in Canada).

q

Do

contact local gas company to ensure gas

meter and gas piping are adequately sized.

q

Do

use teflon tape on water line

connections and fittings.

Don’ts

q

Don’t 

block or restrict Air Intake 

Opening located on the front cover 
of the water heater.

q

Don’t 

remove the front cover unless

absolutely necessary. This should only be
done after being examined by a qualified
service technician.

q

Don’t 

install this product where standing

water may occur.

q

Don’t 

use pipe dope on water line

connections and fittings.

During Installation of this water heater…

Hot and Cold Pipe Insulation Installation

Insulation Blankets

Insulation blankets, available to the general
public for external use on gas water heaters,
are not necessary. The purpose of an
insulation blanket is to reduce the standby
heat loss encountered with storage tank
heaters. This water heater does not store water
making an insulation blanket unnecessary. 

The manufacturer’s warranty does not cover
any damage or defect caused by installation,
attachment or use of any type of energy
saving or other unapproved devices (other
than those authorized by the manufacturer)
into, onto or in conjunction with the water
heater. The use of unauthorized energy saving
devices may shorten the life of the water
heater and may endanger life and property.

The manufacturer disclaims any responsibility
for such loss or injury resulting from the use
of such unauthorized devices.

CAUTION: If local codes require the
application of an external insulation
blanket to this water heater, pay careful
attention to the following so as not to
restrict the proper function and operation
of the water heater:

l

Do not cover the air inlet, flue outlet or
operating and warning labels attached to
the water heater or attempt to relocate them
on the exterior of insulation blanket.

WARNING: If local

codes require external
application of insulation
blanket kits the
manufacturer’s
instructions included
with the kit must be
carefully followed.

NOTICE: The hot and cold
pipes should be insulated as
shown to provide additional
freeze protection.

Water Inlet

Pressure Relief
Valve

Drain Valve

Hot Water Service
Valve

Cold Water

Service Valve

WARNING: In case the

pipe insulation is not rated
for the appropriate
weather conditions install
electric heat tracing or
equivalent to prevent
freezing of the pipes. Do
not insulate or block drain
valve on the hot outlet
fitting. If the pipes are
allowed to freeze, the water
heater and the pipes may
malfunction or leak due to
freezing water.

Pipe Insulation

Содержание PH-28C IFSN

Страница 1: ...r to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is very important that all persons who are expected...

Страница 2: ...THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is nee...

Страница 3: ...well as other flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combus...

Страница 4: ...switch adjustment Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is supplying general purpose ho...

Страница 5: ...P gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level l Before attempting to light the water heater make sure to loo...

Страница 6: ...ATION READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage...

Страница 7: ...which may result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc l The water heater s...

Страница 8: ...hich may be improperly stored or accidentally spilled l The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for...

Страница 9: ...ghly corrosive after passing through a flame The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere NOTICE The water heater should not be installe...

Страница 10: ...ctions in this manual before completing the installation and putting the water heater into service DANGER Failure to install the appliance vent adapter and properly vent the water heater to the outdoo...

Страница 11: ...he appliance vent adapter manufacturer s instructions A B High Temp Sealant Collar Appliance Vent Adapter Clamp Water Heater Exhaust Flow Draining the Condensate Provision should be made to collect an...

Страница 12: ...de of opening 1 foot 300 mm above opening 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3kW and 50 000 Btuh 15kW 12 inches 30 cm for appliances 50 000 Btuh 1...

Страница 13: ...d not contain substances that corrode the vent pipe Do NOT extend exposed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Install outdo...

Страница 14: ...alls Reinstall the decorative sheathing around the Wall Thimble This assembly may be painted to match the exterior decor l Attach a Paloma approved 4 10 cm screened 90 elbow termination to the female...

Страница 15: ...to Combustibles Firestop Firestop Roof Jack Adjustable Roof Flashing Vent Adapter 3 8 cm Clearance Support Hanger Condensate Trap To Drain Dispose of condensate in accordance with local codes Storm C...

Страница 16: ...both cold and hot water supply lines DO NOT cover the drain or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed l Operati...

Страница 17: ...ded on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check Valve between the water heater and the water shutoff valve see the top lef...

Страница 18: ...codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T P relief valve or...

Страница 19: ...force over 31 5 ft lbs 42 7 Nm in tightening the pipe particularly if teflon pipe compound is used as the unit may be damaged The inlet gas pressure to the water heater must not exceed 10 5 w c 2 6 k...

Страница 20: ...ust comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 or in Canada Canadian Electrical Code CSA C22 1 Part 1 20 Installing t...

Страница 21: ...the remote control cables to the extension cable from the water heater l l Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in the remote con...

Страница 22: ...ther equipment that carry a ground fault interrupter l An ON OFF switch must be provided and installed for the incoming 120VAC power l Wire the water heater exactly as shown below A wiring diagram is...

Страница 23: ...l codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions Vacuum Relief Valve Not Supplied If required install per local...

Страница 24: ...ket is to reduce the standby heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover...

Страница 25: ...pply q Gas type matches rating plate q Gas supply pressure is sufficient for the water heater q Gas line equipped with shut off valve union and sediment trap q Approved pipe joint compound used q Soap...

Страница 26: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Страница 27: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Страница 28: ...the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burner if the water heater...

Страница 29: ...d or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply Vacuum a...

Страница 30: ...rner flame Blue flames should be seen when the main burner is firing If any unusual burner operation is noted the water heater should be shut off until qualified service assistance can be obtained CAU...

Страница 31: ...eezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from insta...

Страница 32: ...lfunctions if applicable l Check and replace if necessary Error code displayed on remote control l See instructions for Error Code and if required contact a dealer for service Not enough water demand...

Страница 33: ...material or vent configuration l Open the Gas shutoff valve fully l Contact gas utility company l Fill up LP Gas container or replace with a new cylinder of LP Gas l Bleed all air from gas lines l Ens...

Страница 34: ...late Specify type of gas natural or LP as marked on the rating plate Part description as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring gas...

Страница 35: ...o 120 F 49 C Follow first four bullets points listed above then continue as listed below l Press the SW1 button on the left hand side of the PCB for more than 1 second The LED on the PCB starts illumi...

Страница 36: ...omplete satisfaction you should then contact the following address 2151 Eastman Avenue Oxnard CA 93030 Phone 805 278 5499 When contacting the manufacturer the following information will be requested a...

Страница 37: ...line without the use of a temperature sensor timer or a continuously operating pump All Applicable Warranty Periods will be limited to one 1 year from the Effective Date if the water heater is instal...

Страница 38: ...ter heater or component part s Paloma will not reimburse any party for these or any other fees not specifically covered in this Limited Warranty document HOW TO OBTAIN WARRANTY CLAIM ASSISTANCE Any cl...

Страница 39: ...moved or the date of purchase of the part If it was purchased separately to establish the In warranty status of the defective component part If Paloma determines that the water heater or component par...

Отзывы: