- 18-
P02
AC temp differentia
2~15
℃,
minus differentia
2
℃
P03
Coil copper pipe temp to active defrost
-20~5
℃
0
℃
P04
water source side anti freeze temp
(for Geo heat pump)
-20~5
℃
2
℃
P06
Coil copper pipe temp to stop defrost
10~35
℃
30
℃
P07
defrost time (defrost action lasting max time, will stop defrost if
longer than this value)
15~99 minutes
15
P08
defrost interval time ( time between 2defrosts, less than this value, it
will not defrost)
15~99 minutes
35
P09
ambient temp to activate hot water e-heater
-20~20
℃
0
℃
P10
ambient temp to activate AC e-heater
-20~20
℃
0
℃
P11
DHW frequency limitation percentage on max frequency.
(If heat pump max is 90HZ, p11=9, DHW only run 81hz)
2~10
,
(equal to the highest
frequency 20~100%)
10
P12
compressor discharge air protection temp (higher than the setting, it will
protect)
100~127
℃
115
℃
P13
defrost interval multiple times control
(if P08=35minutes, P13=2, interval between defrost will be
35*2=70Minutes)
0
:
no defrost
;
1~4
;
defrost interval
time multiple rate
1
P14
functional parameter ( to control seasonal valve and solar valve,
UK may not use it)
0
:
G3 is seasonal switching valve
;
1
:
G3is solar valve
;
0
P19
running with fixed frequency
(for factory testing only)
10~100 HZ
50HZ
P20
running frequency setting
( for factory only)
0
:
manual frequency
;
1
:
auto running frequency
1
P21
EEV manually initial open degree (heating) /2
50~240 (Only valid when P23=3)
175
P22
EEV manually initial open degree (cooling)/2
50~240(Only valid when P23=3)
175
P23
EEV control mode
0—no
;
1—checking
;
2—manual
;
3—auto
for factory only
0
P24
EEV Temp differential to stop the valve (heating)
-5~10
℃
for factory only
0
℃
P25
EEV temp differential to stop the valve (cooling)
-5~10
℃
for factory only
0
℃
P26
water pump working mode
0(no stop)
、
1
(
stop when reach temp
)、
2
(
running 1 minute every 15minutes
)
1
P27
second heat source validation
0
(
no
)
、
1
(
yes
)
0
P28
starting air temp for second heat source
-30~15
℃
(On when lower than this)
-15
℃
P29
room target setting temp
10-28
℃
21
℃
(
H
)
P30
buffer tank highest temp
35-55
℃
45
℃
(
G
)
P31
buffer tank lowest temp
15-30
℃
25
℃
(
L
)
P32
water temp adjust range
1-5
℃
2
℃
(
F
)
P33
water temp adjust interval
20-255min
120min (
I
)
P34
longest counting period
6-48H
24H
(
J
)
P35
target water temp modification value
-2
℃
-5
℃
2
℃
(
E
)
P36
ambient temp correction factor X100
10-200
75
(
C
)
P37
starting ambient temp for calculation
-7-15
℃
7
℃
(
B
)
P38
temp differential to reduce frequency
4-15
℃
7
℃
(
T
)
P39
target of low frequency(when reach the setting of P38, it will
reduce to the P39/100 of the highest
15-90
15
(
U
)
P40
monitoring interval (to adjust frequency)
1-15min
2min
(
V
)
P41
temp interval (increase or decrease base on this setting. Every P40
minutes when reach P41 C/2, will change frequency)
1-4
℃
1
℃
(
W
)
P42
increase frequency adjustmentX100
2-50(%)
15
(
S
)
P43
decrease frequency adjustment X100
2-50 (%)
15
(
Y
)
P44
target temp tolerance
1-3
℃
2
℃
(
Z
)
P45
AC AU curve offset value (our weather compensation curve AU)
-15~15
℃
0
℃
P46
AC AU curve max temp value (our AU)
30~50
℃
45
℃
P47
night mode validation (night mode: DHW increase 3C,
AC temp reduce 2C)
0
(
off
)
、
1
(
on
)
0
P48
night mode starting point
0-23
(
time
)
22
P49
night mode ending point
0-23
(
time
)
6
Remarks:
1.
The Parameter P21~P25 are different for different modles, it can
only be set during the production. You have to keep it during your
Содержание AH11
Страница 1: ... 1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8 ...
Страница 9: ... 9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing ...
Страница 21: ... 21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S ...
Страница 22: ... 22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S ...