![Palm AC Series Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/palm/ac-series/ac-series_installation-and-operation-manual_748325021.webp)
After finish the installation tasks, please check the items:
1 Check the dip switch setting and short wiring as shown below to be sure of correct electricty connection
.
The DIP switch can only be set at factory or by authorized engineer
Any improper setting may cause
unrecoverable damage or misfunction
.
.
2 cable
3
Water circuit
Check if the power cable is connected correctly, and check if the screws have been screwed down.
Check if the water pipes are correctly connected, and the pipe dimensions are correct.
Check if all the shut off valve and manual valve is opened, check if all the joint is fastened.
Heatproof measures must be taken for water outlet pipes and water inlet.
Please use specified
cables.
communcation
Turn on the heat pump
select
or not,t
cooling, heating, domestic hot water mode , check whether the unit is running properly
he
compressor will be started in 3~5 minute after powered on.
:
.
Note
Please only select heating model before assuring the water pump is working properly
SW4 1
Single phase:
- :
ON
1 2
4
Three phase:
’
Running
7 Test Run
7 1 Preparation
.
Before fill the water to heat pump water system
please make sure the whole water system is
connected correctly
all the piping joints are fasten good
,
,
.
’
Our heat pump has antifreeze function if the electricity is connected. So please keep the electricity always
connected even when you don t use the heat pumps
If you don t want to use the heat pumps for
long time in winter or if the electricity is cut off by accident for more than 30 minutes, you need to drain out
all the recycling water to protect the heat pump to be freezen.
In cold area
for the safety, you d better use brine as the fluid in the heat pump water system instead of
pure water. If the lowest air temperature come to -10°C , you need add 25% C2H602 (Ethylene glycol) to the
clean pure water. If the lowest air temperature come to -25°C, you need to add 40% C2H602 to the clean
water.
'
.
'
,
'
Important Notice for Antifreeze to Avoid heat pump broken
Two method of water filling
1
For similar installation system as installation method 1, please open the tap water valve, open ball valve
10, air discharge valve 15 and water tank air discharge valve, until the water is full. Then close air discharge
valve15 , ball valve 10 and water tank air discharge valve.
2
For similar installation system as installation method 2,
please open the tap water valve, open ball valve
10, 15, air discharge 16, air discharge 17 and water tank air discharge valve, until the water is full. Then close
air discharge valve 16,17, ball valve10,15 and water tank air discharge valve.
、
、
,
7 2 Water filling
.
19
3
ON
1 2
4
3
T R A N
N 4
N 3
N 2
N 1
N 1 0
N 1 2
N 1 1
N 1 3
S W 4
A n 6
A n 1
ON
1 2
4
3
S w 5
ON
1 2
4
3