16
004723012 - 05/05/2022
ALARM hysteresis thermostat
IE03
1
2
40
[°C]
FAN SAFETY hysteresis thermostat
IE04
1
2
40
[°C]
Opening Valve hysteresis thermostat
IE05
1
2
40
[°C]
Closing Valve hysteresis thermostat
IE06
1
2
40
[°C]
SERVICE output Activation hysteresis
thermostat
IE07
1
2
40
[°C]
Room temperature hysteresis thermo-
stat
Ib01
0
1
20
[°C]
Fan Speed P01 (minimum)
UA01
20
1
100
[%]
Fan Speed P09 (ninth)
UA09
80
1
100
[%]
Fan Speed P10 (maximum)
UA10
100
1
100
[%]
Delay Time Damper Closing
t 06
0
10
120
[min]
Time of suspension of Acoustic alarm
t 07
1
5
60
[min]
Time of Fan Starting
t 08
0
2
10
[sec]
Input Configuration S2; 0 = not used; 1
= Probe; 2 = Thermostat
P01
0
0
2
n
SERVICE Output Configuration
P02
0
0
3
n
Enabling FAN SAFETY
P03
0
1
1
n
Enabling Air SAFETY
P04
0
1
1
n
Enabling Air ALARM
P05
0
1
1
n
Enabling Damper Start Function
P12
0
0
1
n
Input Configuration S2; 1 = Probe; 2 =
Thermostat
P17
1
1
2
n
NOTES
: Modifying
UA01
,
UA09
,
UA10
, the Fan immediately goes to the speed
that you are calibrating in order to see the effect.