TYPE TUBE RADIANT HEATER
User’s Manual
8
•
SOLELY INTERIOR installation is possible.
•
The installation must comply with the valid standards.
•
For the sake of appropriate effeciency the position and the high of installation has to be carefully defined.
•
The appliance has to be placed in that way that its every part be accessible.
WARNING! Only a qualified person can install the appliances who participated in training which was
organised by Pakole Trade Kft in every year. It is forbidden to install the device as an user.
Appliance installation
Attachment of flexible gas pipe has to be directly to the outside threaded gas connection of appliance located on the back side of it.
Works to be performed during gas connection
•
Gas pipes cleaning
The thorough cleaning of gas-supply system is very important before attachment of appliance.
•
Gas leakage checking
After installation of appliance make sure about leak-proof mounting of connections. This action must be fulfilled after every dis
-
mounting and assembling!
ATTENTION! Both the fan and the ignition control needs 230V/50Hz mains voltage.
Before connecting the appliance to the gas pipe line, please disconnect it from the power line and
close the gas valve front of the burner. The appliance must be connected to a grounded power supply
system!
If the above instructions are not followed that can lead to death, heavy injuries or property demages!
PLEASE CHECK THE EARTHING!
VIGYÁZAT
!
VESZÉLY
!
VIGYÁZAT
!
ÁRAM
ELLÁTÁS
FIGYELEM
!
FÖLDELÉS
KIALAKÍTÁSA
SZÜKSÉGES
Electrical connection
The combustion–air supply centrifugal fan is fixed to the appliance/burner head, the automatic burner control is located in the burner
head in this way the electrical supply has to be installed just into the appliance head.
•
ELECTRICAL CONNECTING SPECIFICATIONS:
•
The appliance/burner head can be connected to the mains by safety electrical connector (Fig.13) located on the fan side
of appliance head.
•
The appliance must be operated under dry circumstances.
•
At electrical installation of appliance the relevant MSZ 2364 standard must be considered.
• The mains connection can be executed by grounded plag or fixed properly installed phase-null wires.
•
The appliance is phase-sensitive for this reason the connection always must be according to the Fig.13.
• Fort he sake of suitable detachability of appliance from the electrical supply, double-pole – phase / null switching off – detaching ma
-
in-switch must be installed.
•
Electrical wiring: 3 x 0,75 MT cable
•
Fuse: 2A dissolving fuse
•
Before change of dissolving fuse by disconnecting of Hirschmann plug the appliance must be detached from electrical supply.
4.picute: Electrical connection
L PE N
FU
SE
NM
VeL
N
L1
LT
VL
VN
SL
V.1
5-1
C
FAN
VL
VN
SL
PE
12 11 10 9
8
7
6
5
4
3
2
1
SIT 579 DBC
APS
14
13
Green
Red
Pici Hirschmann
845 SIGMA
Segéd
szelep
L
PE
N
Error sign