FORCED CONVECTION AIR HEATERS
Instructions for Installation and Servicing
Recommended temperature regulators for appliances:
Please find the description of termostats in supplied with these
21. picture: AHP-1, AHP-2, AHP-3, AHP-MOD type of termostat
Optional accessories
Temperature controllers
• The mains fuse should be inactive characteristic-type and for definition of its value take the nominal current consumption - indicated
on the data board - of device respectively the quantity of devices moreover in case of bigger distances the length of mains wiring
into account�
• The mains wire must be installed in the fixed way.(The appliance can not be attached to the mains by plug !)
•
The proper installation of phase-null wires have to be thoroughly checked !
•
The appliance has I-class protection against electric shock for this reason it must be supplied with wired protection against electric
shock!
•
The appliance must be operated under dry circumstances�
•
At electrical installation of appliance the relevant standard must be considered�
• For the sake of suitable detachability of appliance from the electrical supply, double-poles – phase / null switching off – detaching
main-switch must be installed�
•
This main switch must be lockable-type in „OFF” position (e�g� by padlock)�
• In case of specification of the main switch,the nominal current consumption of appliance moreover the instruction of 2014/35/EU
must be considered�
Electrical connecting specification