© 2014 Packet Power LLC www.packetpower.com EM31.2
8
The E312 utilizes a different mounting bracket (shown below). It comes
standard with the unit as it is required to allow access to the battery
storage area once the unit has been installed. It comes with an adhesive
pad and sheet metal screws and can also be fastened with tie wraps.
NODE SPACING AND OPERATIONAL MODES:
Monitoring units must be within 10 to 30 meters (30-100 feet) of another monitoring unit or a
Gateway. The network will automatically optimize how traffic flows over the network.
In order to maximize battery life, E312 units change behavior when operating on battery power:
o
Battery units do not act as relays for other Packet Power devices.
o
Battery units must be able to communicate directly with one of the following:
E312 or E306 Environmental Monitors operating on AC power
GW03-XXXX Ethernet Gateways (firmware 6.4.1 or later)
Power monitoring models RGXX-, PGXXX- or MGXX- (firmware 10.22 or later)
o
The button on the unit must be held down to start the firmware upgrade process.
o
Plugging the AC power supply into an E312 prevents the unit from using battery power even
if AC power is lost.
E312 Mounting
Bracket
Packet Power Mesh Network