packardonline.com | 800.334.1769 5

Using EC Max to replace PSC (Permanent Split Capacitor) induction motors.

• Install motor in HVAC system using a belly band mount.

 •     Select the voltage plug that matches the voltage rating of the replaced motor. 

Install the voltage plug. Connect the harness plugs to the motor. 

White Voltage Plug

115vac Systems

Yellow Voltage Plug

230vac Systems

• HIGH VOLTAGE POWER CONNECTIONS

 

 Note: The Black and White HIGH VOLTAGE POWER wires are taped together and 

flagged for identification.

  Connect the Black HIGH VOLTAGE POWER wire to a L1 line voltage power 

source that is continuously powered when the unit disconnect is closed

  Connect the White HIGH VOLTAGE POWER wire to a Neutral (115vac    

systems) or L2 (230vac systems) that is continuously powered when the 

unit disconnect is closed.

• HIGH VOLTAGE SIGNAL CONNECTION

  

Note: The Black and Red HIGH VOLTAGE SIGNAL wires are taped together and flagged 

for identification.

  Connect the Black (HV1) HIGH VOLTAGE SIGNAL wire to all of the motor 

output terminals from the HVAC board (or fan relay) including Heat, Cool 

and Continuous Fan (if applicable) that were previously connected to the 

PSC motor. Use the supplied jumper wires and terminals or wire nut all 

together.

 Insulate the Red (HV2) HIGH VOLTAGE SIGNAL wire with a wire nut.

• LOW VOLTAGE SIGNAL CONNECTIONS

 

 Note: All LOW VOLTAGE SIGNAL wires are taped together and flagged for              

identification.

  Connect the Blue LOW VOLTAGE SIGNAL wire to the thermostat common 

terminal or directly to the common side of the 24vac transformer.

  Connect the speed desired for HEAT to thermostat (W) and the speed    

desired for COOL (including A/C or Heat Pump systems) to thermostat (Y).

• NOTE: 

  After completing all connections, the technician should operate the system in 

all demand modes measuring airflow using industry best practices. To adjust 

the airflow, change the speed selection connected to the appropriate thermostat 

terminal. 

  If the system has a Continuous Fan selection at the thermostat, this demand 

will energize the motor through the fan relays to energize the Black (HV1) HIGH 

VOLTAGE SIGNAL input which will operate the motor at the default continuous fan 

speed. This speed is approximately 200 rpm slower than the LOW speed from the 

LOW VOLTAGE SIGNAL CONNECTIONS. If a higher continuous fan speed is desired, 

connect any unused speed selection to thermostat terminal (G).

Содержание Ec Max

Страница 1: ...Electronically Commutated Motor Wiring Manual R 0 G 105 B 62 00693e GREEN SPECS R 0 G 0 B 0 000000 BLACK SPECS FONT Arial Bold...

Страница 2: ...packardonline com 800 334 1769 2 Table of Contents Safety Considerations 3 Application Guide 4 5 6 7 8 Operational Characteristics 9 10 11 12 Diagnostics Maintenance Warranty 13 Specifications 14...

Страница 3: ...applying power to this motor Use of the wires provided in this kit is recommended Should additional wires be needed use equivalent size wire gauge and rated insulation Improper installation adjustment...

Страница 4: ...In this manual there are two sets of instructions One for replacing PSC motors and one for replacing Constant Torque ECM Please make sure to use the correct instructions for the motor you are replaci...

Страница 5: ...nuous Fan if applicable that were previously connected to the PSC motor Use the supplied jumper wires and terminals or wire nut all together Insulate the Red HV2 HIGH VOLTAGE SIGNAL wire with a wire n...

Страница 6: ...packardonline com 800 334 1769 6 Using EC Max to replace PSC Permanent Split Capacitor induction motors...

Страница 7: ...ed HV2 HIGH VOLTAGE SIGNAL wire to a L1 line voltage power source that is continuously powered when the unit disconnect is closed This wire can be connected to the same L1 source as the Black HIGH VOL...

Страница 8: ...packardonline com 800 334 1769 8 Using EC Max to replace Constant Torque ECM...

Страница 9: ...itself When the Red wire is energized the LOW VOLTAGE SIGNAL wires provide both the ON OFF command for the motor and determine the output level speed The LOW VOLTAGE SIGNAL wires provide the speed sel...

Страница 10: ...nent Split Capacitor induction motors Example connection using the optional Y adapter when replacing PSC motors Using EC Max to replace Constant Torque ECM Example connection of one speed to multiple...

Страница 11: ...s life It will never perform this function again If this is not the correct direction it can be reversed Changing the rotation of the motor after it has selected a rotation using the process above is...

Страница 12: ...69 12 Wiring diagram for changing the rotation of the motor Using EC Max to replace PSC Permanent Split Capacitor induction motors Wiring diagram for changing the rotation of the motor Using EC Max to...

Страница 13: ...purpose Buyer acknowledges that it alone has determined that the goods purchased will suitably meet the requirements of their intended use In no event will Packard be liable for consequential incident...

Страница 14: ...ED HI HI Rotation CW or CCW automatically configured Bearing Ball Ambient Rating 40 C Enclosure Open Air Over OAO Frame size and dimensions NEMA 48 Frame 5 6 diameter see diagram below for DIM A B 1 3...

Страница 15: ...packardonline com 800 334 1769 15...

Страница 16: ...e Headquarters and Main Distribution Center 2700 Barrett Lakes Blvd NW Suite 100 Kennesaw GA 30144 Distribution Centers 2570 N Shadeland Ave Suite 103 Indianapolis IN 46219 6151 W Erie St Chandler AZ...

Отзывы: