background image

packardonline.com | 800.334.1769 11

Rotation

 is determined automatically the first time the motor is operated. It 

is important to operate the motor for the first time in the HVAC system. Do 

not bench test the motor. The first time the motor is operated the following         

sequence should be recognized:

•  The motor will run very slowly in CW rotation (lead end) for approximately 15 

seconds then stop.

•  The motor will run very slowly in CCW rotation (lead end) for approximately 

15 seconds.

• The motor will then either:

increase speed (related to the speed selection energized) at the current 

CCW rotation if that is the direction it has selected;

or stop, reverse to CW rotation and increase speed to CW rotation. 

Once the motor speeds up, the direction the motor is operating is the 

direction it has selected. It will now start and run in this direction the rest 

of its life. It will never perform this function again. If this is not the correct 

direction it can be reversed. 

Changing the rotation of the motor after it has selected a rotation using the        

process above is accomplished with the following steps. 

• Turn off the power to the HVAC system.

• Leave the HIGH VOLTAGE POWER wires connected 

•  Connect both the Black and Red (HV1 & HV2) HIGH VOLTAGE SIGNAL 

WIRES to the same L1 source as the Black HIGH VOLTAGE POWER wire.

• Leave the Blue LOW VOLTAGE SIGNAL wire connected to 24vac common.

•  Disconnect all the LOW VOLTAGE SIGNAL speed wires from the motor to the 

HVAC system controls.

•  Connect the White (Low Speed) LOW VOLTAGE SIGNAL wire only to the 

thermostat (R) terminal or directly to 24vac side of the transformer. 

•  Restore power to the HVAC system. There is no need for a thermostat       

demand. Set a stop watch for 1 minute. 

•  After 1 minute, turn off the power to the HVAC system and restore all wires to 

the desired configuration for the application.

• The next time the motor is energized it will operate in the opposite direction. 

Содержание 46001

Страница 1: ...Electronically Commutated Motor Wiring Manual R 0 G 105 B 62 00693e GREEN SPECS R 0 G 0 B 0 000000 BLACK SPECS FONT Arial Bold ...

Страница 2: ...packardonline com 800 334 1769 2 Table of Contents Safety Considerations 3 Application Guide 4 5 6 7 8 Operational Characteristics 9 10 11 12 Diagnostics Maintenance Warranty 13 Specifications 14 ...

Страница 3: ... applying power to this motor Use of the wires provided in this kit is recommended Should additional wires be needed use equivalent size wire gauge and rated insulation Improper installation adjustment alternation service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal injury death or property damage Consult a qualified installer service ag...

Страница 4: ...E In this manual there are two sets of instructions One for replacing PSC motors and one for replacing Constant Torque ECM Please make sure to use the correct instructions for the motor you are replacing to prevent damage to the motor NOTE The EC Max is mounted using a belly band mount The mount is not provided If the replaced motor used a belly band and was a NEMA 48 Frame motor the original bell...

Страница 5: ...inuous Fan if applicable that were previously connected to the PSC motor Use the supplied jumper wires and terminals or wire nut all together Insulate the Red HV2 HIGH VOLTAGE SIGNAL wire with a wire nut LOW VOLTAGE SIGNAL CONNECTIONS Note All LOW VOLTAGE SIGNAL wires are taped together and flagged for identification Connect the Blue LOW VOLTAGE SIGNAL wire to the thermostat common terminal or dir...

Страница 6: ...packardonline com 800 334 1769 6 Using EC Max to replace PSC Permanent Split Capacitor induction motors ...

Страница 7: ...Red HV2 HIGH VOLTAGE SIGNAL wire to a L1 line voltage power source that is continuously powered when the unit disconnect is closed This wire can be connected to the same L1 source as the Black HIGH VOLTAGE POWER wire in the previous step Insulate the Black HV1 HIGH VOLTAGE SIGNAL wire with a wire nut Note This wire can be connected to the same terminal as the L1 HIGH VOLTAGE POWER connection in th...

Страница 8: ...packardonline com 800 334 1769 8 Using EC Max to replace Constant Torque ECM ...

Страница 9: ... itself When the Red wire is energized the LOW VOLTAGE SIGNAL wires provide both the ON OFF command for the motor and determine the output level speed The LOW VOLTAGE SIGNAL wires provide the speed selection to the motor These are 24vac inputs The low voltage signal inputs are programmed with a hierarchy If more than one input is energized at the same time the higher tap value speed value will be ...

Страница 10: ...anent Split Capacitor induction motors Example connection using the optional Y adapter when replacing PSC motors Using EC Max to replace Constant Torque ECM Example connection of one speed to multiple fan relay outputs from the HVAC system control board or fan relay s ...

Страница 11: ...ts life It will never perform this function again If this is not the correct direction it can be reversed Changing the rotation of the motor after it has selected a rotation using the process above is accomplished with the following steps Turn off the power to the HVAC system Leave the HIGH VOLTAGE POWER wires connected Connect both the Black and Red HV1 HV2 HIGH VOLTAGE SIGNAL WIRES to the same L...

Страница 12: ...769 12 Wiring diagram for changing the rotation of the motor Using EC Max to replace PSC Permanent Split Capacitor induction motors Wiring diagram for changing the rotation of the motor Using EC Max to replace Constant Torque ECM ...

Страница 13: ... purpose Buyer acknowledges that it alone has determined that the goods purchased will suitably meet the requirements of their intended use In no event will Packard be liable for consequential incidental or other damages 3 For products other than those listed below please MAIL the original nameplate label or sticker for each item Copies of labels will NOT be accepted Please do NOT fax or email lab...

Страница 14: ...MED HI HI Rotation CW or CCW automatically configured Bearing Ball Ambient Rating 40 C Enclosure Open Air Over OAO Frame size and dimensions NEMA 48 Frame 5 6 diameter see diagram below for DIM A B 1 3 Hp DIM A 11 26 DIM B 6 34 1 2 Hp DIM A 11 26 DIM B 6 34 3 4 Hp DIM A 12 76 DIM B 7 84 1 Hp DIM A 12 76 DIM B 7 84 Shaft 5 x 5 4 5 single flat Mounting Belly band not supplied Harness Lead length 48 ...

Страница 15: ...packardonline com 800 334 1769 15 ...

Страница 16: ...te Headquarters and Main Distribution Center 2700 Barrett Lakes Blvd NW Suite 100 Kennesaw GA 30144 Distribution Centers 2570 N Shadeland Ave Suite 103 Indianapolis IN 46219 6151 W Erie St Chandler AZ 85226 Packard supplies to wholesale distribution only PACKARDONLINE COM ...

Отзывы: