SECTION 3
INSTALLATION
24
3.4.1 CONFIGURE TRANSFORMER RATIO
NOTE:
Most users will not need to concern themselves with the unit configuration as it is set at the
factory if the UPC is packaged with a power source.
Set the TRANSFORMER RATIO of the UPC to be the same as the turns ratio of the Output XFMR in the
Power Source. Refer to the Power Source Manual to determine the TRANSFORMER RATIO of the
Power Source. The ratio is set by the TRANSFORMER RATIO SWITCH on the UPC METERING PCB.
See figure 3.4.1. The Dip-switches S2-8 and S1-1 thru S1-8 are binary weighted:
RATIO
DIP-SWITCH SETTING
S1-8 S1-7 S1-6 S1-5 S1-4 S1-3 S1-2 S1-1 S2-8
WEIGHTING
VALUE
2.56
1.28
.64
.32
.16
.08
.04
.02
.01
NO
XFMR
*
OFF OFF OFF OFF OFF OFF OFF OFF OFF
0.50
OFF OFF OFF ON ON OFF OFF ON OFF
1.00
OFF OFF ON ON OFF OFF ON OFF OFF
1.50
OFF ON OFF OFF ON OFF ON ON OFF
2.00
OFF ON ON OFF OFF ON OFF OFF OFF
2.50
OFF ON ON ON ON ON OFF ON OFF
5.11
ON ON ON ON ON ON ON ON ON
* Set all bits to OFF to indicate NO TRANSFORMER installed.
NOTE:
TRANSFORMER RATIOs are implied as a ratio to one, e.g., a setting of 2.5 is implied as a ratio
of 2.5:1.
Содержание UPC-32
Страница 1: ...UPC 32 UPC 12 PROGRAMMABLE CONTROLLERS FIRMWARE V2 53 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE...
Страница 2: ......
Страница 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK...
Страница 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12...
Страница 46: ...SECTION 4 OPERATION 34 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL...
Страница 77: ...SECTION 4 OPERATION 65 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM...
Страница 139: ...NOTES 127 NOTES...
Страница 140: ...MODIFICATIONS 128 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made...